Auto-Charged Capacitor Trip Device
The MODEL 410 Auto-Charged Capacitor Trip Device provides essential standby power for critical applications. This unit features a self-contained power source, ensuring operational continuity even during primary power interruptions. With a 4,000mAh, 1.2v, 'D' cell NiCad battery, it maintains full operating voltage for a minimum of two days, offering reliable performance. Its robust design includes a cover-actuated safety switch, which discharges the capacitor and disconnects the primary source upon cover removal, enhancing operational safety. The device operates within a -20° to +131° F temperature range and tolerates 0-97% humidity without condensation. This ensures dependable functionality in diverse industrial environments. Its 380VDC minimum output voltage and 28.7 watt seconds output power support demanding requirements. The unit's 120VAC nominal input and surface mounting capability simplify integration.
Auto-Chrg Trip Dev
Specifications
| Nominal AC voltage (phase to phase) | 120VAC |
|---|---|
| Input voltage range | 108-132VAC |
| Frequency | 60Hz |
| Battery | 4,000mAh, 1.2v, 'D' cell NiCad (user replaceable) |
| Output voltage | 380VDC minimum |
| Output power | 28.7 watt seconds |
| Operating temperature | - 20° to +131° F |
| Humidity tolerance | 0 - 97% w/o condensation |
| Case material | 20 gauge CRS |
| Mounting | Surface |
| Agency approval | UL Recognized |
| Feature | Self-contained standby power source |
| Standby Power Duration | Maintains full operating voltage for a minimum of two days |
| Discharge Method | Manually, or with an external control device |
| Safety Feature | Cover-actuated safety switch, which discharges the capacitor and disconnects the primary source when the cover is removed |