Auto-Charged Capacitor Trip Device

The MODEL 410 Auto-Charged Capacitor Trip Device, SKU 410-230, offers a reliable solution for critical power applications. This unit features a self-contained standby power source, ensuring continuous operation even during primary power interruptions. Its integrated 4,000mAh, 1.2v, 'D' cell NiCad battery maintains full operating voltage for a minimum of two days, providing extended operational readiness. The device delivers a minimum output voltage of 380VDC and 28.7 watt seconds of output power, suitable for demanding industrial requirements. Designed for surface mounting, its 20 gauge CRS case material ensures durability. A cover-actuated safety switch enhances operational security by discharging the capacitor and disconnecting the primary source upon cover removal. UL Recognized approval confirms its adherence to established safety standards. This device provides consistent performance across an operating temperature range of -20° to +131° F, making it suitable for diverse environmental conditions.

Auto-Chrg Trip Dev

Specifications

Nominal AC voltage (phase to phase)208/230VAC
Input voltage range216-264VAC
Frequency60Hz
Battery4,000mAh, 1.2v, 'D' cell NiCad (user replaceable)
Output voltage380VDC minimum
Output power28.7 watt seconds
Operating temperature- 20° to +131° F
Humidity tolerance0 - 97% w/o condensation
Case material20 gauge CRS
MountingSurface
Agency approvalUL Recognized
FeatureSelf-contained standby power source
Standby Power DurationMaintains full operating voltage for a minimum of two days
Discharge MethodManually, or with an external control device
Safety FeatureCover-actuated safety switch, which discharges the capacitor and disconnects the primary source when the cover is removed

FAQs

What is the standby power capability of the 410-230 Auto-Charged Capacitor Trip Device?
The device includes a 4,000mAh, 1.2v, 'D' cell NiCad battery that maintains full operating voltage for a minimum of two days, providing self-contained standby power.
What are the electrical specifications for the 410-230 unit's operation?
The 410-230 operates with a nominal AC voltage of 208/230VAC, an input voltage range of 216-264VAC at 60Hz, and delivers a minimum output voltage of 380VDC with 28.7 watt seconds of output power.
What safety features are integrated into the 410-230 Auto-Charged Capacitor Trip Device?
The unit incorporates a cover-actuated safety switch. This mechanism discharges the capacitor and disconnects the primary source when the cover is removed, enhancing operational safety.