Model 295-120 Capacitor Trip Device
The Model 295-120 Capacitor Trip Device provides essential circuit breaker tripping capabilities for industrial systems. Designed for operational continuity, it accepts a nominal 120VAC input, delivering a stable 170VDC output. A key feature is its hold-up time, guaranteeing at least 12 seconds of power after input voltage removal, crucial for maintaining system integrity during transient events. This device operates reliably across a broad 50-400Hz frequency range and withstands environmental conditions from -20° to +131° F. Its robust 20 Gauge CRS construction and surface mounting option ensure durability and ease of installation. With a trip voltage threshold of 65% of normal voltage, the 295-120 offers a dependable solution for critical power management and safety protocols.
Capacitor Trip Device
Specifications
| Nominal input voltage | 120VAC |
|---|---|
| Input voltage range | 90-120VAC |
| Output voltage | 170VDC |
| Frequency range | 50-400Hz |
| Operating temperature | -20° to +131° F |
| Humidity tolerance | 0-97% w/o condensation |
| Case material | 20 Gauge CRS |
| Mounting | Surface |
| Discharge Method | Manually or with a Control Device |
| Initial Current Draw | 10 amps (1st half cycle), 3 amps (2nd half cycle), 1 amp (3rd half cycle) |
| Continuous Current Draw | less than 5 milliamps |
| Hold-up Time | at least 12 seconds after the charging voltage is removed |
| Trip Voltage Threshold | 65% of normal voltage |
| Indicator Threshold | 85 volts or more |
| Warranty | one year |