Model 295-240 Capacitor Trip Device
The Model 295-240 Capacitor Trip Device ensures reliable circuit breaker tripping in industrial environments. Designed for a nominal input voltage of 240VAC, it provides a stable 339VDC output. This device maintains a charge for at least 12 seconds after the charging voltage is removed, a critical feature for facilitating essential tripping functions during power interruptions. Its robust construction allows operation across a wide temperature range of -20° to +131° F and tolerates 0-97% humidity without condensation. The unit's frequency range of 50-400Hz further enhances its adaptability across various power systems. With a continuous current draw of less than 5 milliamps, it offers efficient operation. This device provides consistent performance for critical safety applications, ensuring operational continuity and equipment protection through its dependable trip voltage threshold of 65% of normal voltage.
Capacitor Trip Device
Specifications
| Nominal input voltage | 240VAC |
|---|---|
| Input voltage range | 190-240VAC |
| Output voltage | 339VDC |
| Frequency range | 50-400Hz |
| Operating temperature | -20° to +131° F |
| Humidity tolerance | 0-97% w/o condensation |
| Case material | 20 Gauge CRS |
| Mounting | Surface |
| Discharge Method | Manually or with a Control Device |
| Initial Current Draw | 10 amps (1st half cycle), 3 amps (2nd half cycle), 1 amp (3rd half cycle) |
| Continuous Current Draw | less than 5 milliamps |
| Hold-up Time | at least 12 seconds after the charging voltage is removed |
| Trip Voltage Threshold | 65% of normal voltage |
| Indicator Threshold | 170 volts or more |
| Warranty | one year |