3-Phase Monitor with Adjustable Trip & Restart Delays

20AA-H

The 20AA-H 3-Phase Monitor offers robust protection for critical industrial equipment. This device continuously monitors for phase loss, phase reversal, over/under voltage, and voltage unbalance, ensuring operational integrity. Its adjustable trip delays, ranging from 1 to 30 seconds, allow for precise response tailoring to specific application requirements. Furthermore, the adjustable restart delay, configurable from 1 to 500 seconds, facilitates controlled system recovery after a fault. Operating across a 475-600 VAC range, the monitor integrates seamlessly into diverse three-phase systems. The auto-reset functionality minimizes downtime by automatically re-engaging the system once conditions normalize. LED indicators provide immediate status feedback, simplifying diagnostics. With a 5-year warranty and Noryl plastic enclosure, this unit enhances system reliability and extends equipment lifespan in demanding environments.

Unv 3Ph Monitor

DOWNLOADS:

20aa-h

Specifications

Model TypeAuto Reset
Monitored ConditionsPhase Loss, Phase Reversal, Over/Under Voltage and Voltage Unbalance
IndicatorsLED Status Indicators
Operating Voltage475-600 VAC
Power Consumption4.5W at 600V
Auto RangesNo
Frequency50/60Hz
Type of MeasurementRMS
Under Voltage Trip90% ±1% (% of setpoint)
Under Voltage Reset93% ±1% (% of setpoint)
Over Voltage Trip110% ±1% (% of setpoint)
Over Voltage Reset107% ±1% (% of setpoint)
Voltage Unbalance Trip2-8%, adjustable
Voltage Unbalance ConformanceNEMA
Voltage Unbalance ResetTrip setting minus 0.7%
Trip Delay Time (Over, Under, & Unbalanced)1-30 sec., adjustable
Trip Delay Time (Single-Phasing Faults)1 sec., fixed
Trip Delay Time (Unbalance > 15%)1 sec., fixed
Restart Delay1-500 sec., adjustable
Manual Reset Input5V open circuit/500µA short circuit
Output Contacts2x N.O. (Isolated)
Output Contact Rating7.5A at 240VAC resistive
Operating Temperature-20° to +140° F
Humidity Tolerance0-97% w/o condensation
Terminal Torque3.5 in. lbs. maximum
Wire TypeStranded or solid 14-26 AWG, 1/terminal
Enclosure MaterialNoryl plastic
MountingDIN Rail or Surface Mount
Dimension Tolerance±0.06
Optional Feature/SG = Silver with Gold Flash Contacts
Warranty5-year Unconditional Warranty

FAQs

What voltage range does the 20AA-H monitor operate within?
The 20AA-H monitors systems with an operating voltage between 475-600 VAC.
Can the trip and restart delays be adjusted on the 20AA-H monitor?
Yes, the trip delay is adjustable from 1-30 seconds, and the restart delay is adjustable from 1-500 seconds.
What conditions does the 20AA-H monitor detect?
It monitors for phase loss, phase reversal, over/under voltage, and voltage unbalance.