3-Phase Monitor with Trip & Restart Delays

18-415-50Hz

The MODEL 18 3-Phase Monitor (18-415-50) provides essential protection for industrial systems operating at 415VAC nominal. It detects critical conditions such as phase loss, low voltage, and phase reversal, safeguarding connected equipment from potential damage. Featuring an automatic reset function, operational continuity is maintained efficiently without requiring manual intervention after a fault clears. Users can configure precise trip delays from 1 to 30 seconds and restart delays from 1 to 300 seconds, allowing for tailored system integration and minimizing unnecessary downtime. Its robust design includes SPDT 10 amp output contacts rated at 240VAC resistive and a wide operating temperature range of -20° to +131° F. With a five-year unconditional warranty and UL Recognized approval, this monitor ensures reliable performance, extends equipment lifespan, and enhances system stability in demanding industrial environments.

3Ph Mon

DOWNLOADS:

18-415-50hz

Specifications

DetectionPhase loss, low voltage, phase reversal
Reset TypeAutomatic reset
WarrantyFive year unconditional warranty
Nominal AC (phase to phase)415VAC
Adjustment range340-440VAC
Frequency50Hz
Power consumption3.3W
Transient protection2500VAC for 10ms
Repeat accuracy± 0.1% of set point (fixed conditions)
Trip delay1-30 sec.
Restart Delay1-300 sec.
Dead bandApproximately 2%
Output contactsSPDT 10 amps at 240VAC resistive
Expected relay life (Mechanical)10 million operations
Expected relay life (Electrical)100,000 operations at rated load
Operating temperature-20° to +131° F
Humidity tolerance0-97% w/o condensation
Terminal Torque3.5 in. lbs. maximum
Wire TypeStranded or solid 14-28 AWG, 1/terminal
Enclosure materialNORYL plastic
MountingDIN Rail or Surface Mount
Low Current OptionModels ordered with suffix '/SG' will have silver with gold flash contacts (SPDT 5 amps at 120VAC resistive)
Agency ApprovalUL Recognized (U.S. and Canada)
Usage EnvironmentFor use in a Pollution Degree 2 Environment
Dimension Tolerance± 0.06"

FAQs

What types of electrical faults does the 18-415-50 monitor detect?
The 18-415-50 monitor detects phase loss, low voltage, and phase reversal conditions.
What are the adjustable delay ranges for trip and restart functions on this monitor?
The trip delay is adjustable from 1 to 30 seconds, and the restart delay is adjustable from 1 to 300 seconds.
What are the specifications for the output contacts of the 18-415-50?
The output contacts are SPDT 10 amps at 240VAC resistive, with an expected electrical relay life of 100,000 operations at rated load.