18-380-50Hz

18-380-50Hz

The 18-380-50 3-Phase Monitor provides essential protection for industrial systems. This unit detects critical conditions such as phase loss, low voltage, and phase reversal, safeguarding connected equipment. Featuring an automatic reset function, it ensures operational continuity without manual intervention. Users can configure trip delays from 1 to 30 seconds and restart delays from 1 to 300 seconds, allowing for precise system integration and recovery protocols. Its robust design includes SPDT 10 amp output contacts at 240VAC resistive, suitable for demanding applications. The monitor operates across a wide temperature range, ensuring reliability in diverse industrial environments. UL Recognition further confirms its adherence to established safety standards.

The Model 18 continuously monitors 3-phase power lines for abnormal
conditions. When properly adjusted, the Model 18 monitor will detect
phase loss on a loaded motor even when regenerated voltage is present.
This device consists of a microcontroller with a voltage and phase-angle
sensing circuit, driving an electromechanical relay. When correct
voltage and phase rotation are applied, the internal relay will
energize. A fault condition will de-energize the relay. When the fault
is corrected, the monitor will automatically reset. An adjustable
restart delay prevents short cycling in compressor applications and an
adjustable trip delay prevents nuisance tripping during power
fluctuations. The Model 18 does not require a neutral connection and
can be used with Wye or Delta systems. Voltage ranges are sufficiently
wide to allow for proper adjustment to existing conditions. Both FAULT
and NORM condition indicators are provided to aid in adjustment and
system trouble-shooting. The Model 18 is UL Recognized in the U.S. and
Canada and is available with optional gold flashed silver contacts for
low current applications.

Specifications

DetectionPhase loss, low voltage, phase reversal
Reset TypeAutomatic reset
WarrantyFive year unconditional warranty
Nominal AC (phase to phase)380VAC
Adjustment range300-400VAC
Frequency50Hz
Power consumption3.0W
Transient protection2500VAC for 10ms
Repeat accuracy± 0.1% of set point (fixed conditions)
Trip delay1-30 sec.
Restart Delay1-300 sec.
Dead bandApproximately 2%
Output contactsSPDT 10 amps at 240VAC resistive
Expected relay life (Mechanical)10 million operations
Expected relay life (Electrical)100,000 operations at rated load
Operating temperature-20° to +131° F
Humidity tolerance0-97% w/o condensation
Terminal Torque3.5 in. lbs. maximum
Wire TypeStranded or solid 14-28 AWG, 1/terminal
Enclosure materialNORYL plastic
MountingDIN Rail or Surface Mount
Low Current OptionModels ordered with suffix '/SG' will have silver with gold flash contacts (SPDT 5 amps at 120VAC resistive)
Agency ApprovalUL Recognized (U.S. and Canada)
Usage EnvironmentFor use in a Pollution Degree 2 Environment
Dimension Tolerance± 0.06"

FAQs

What types of phase anomalies does the 18-380-50 monitor detect?
The 18-380-50 monitor detects phase loss, low voltage, and phase reversal conditions in a 3-phase system.
What are the adjustable delay ranges for trip and restart functions on this monitor?
The trip delay is adjustable from 1 to 30 seconds, and the restart delay can be set from 1 to 300 seconds.
What are the electrical specifications for the output contacts?
The output contacts are SPDT rated at 10 amps resistive at 240VAC.