3-Phase Monitor with Adjustable Trip & Restart Delays
The Model 20AB 3-Phase Monitor, SKU 20AB-HM, provides essential protection for industrial systems. It monitors phase loss, phase reversal, over/under voltage, and voltage unbalance, ensuring comprehensive system oversight. Users can adjust trip delays from 1 to 30 seconds for over, under, and unbalanced voltage conditions, allowing for tailored response times to specific operational needs. A manual reset feature ensures controlled system restarts following a fault. Operating across 475-600 VAC with a power consumption of 4.5W at 600V, this unit offers reliable performance in demanding environments. Its robust design includes a Noryl plastic enclosure and flexible DIN rail or surface mounting options. The monitor's precise RMS measurement type contributes to accurate fault detection, minimizing downtime and protecting valuable equipment from electrical anomalies.
Unv 3Ph Monitor
Specifications
| Reset Type | Manual Reset |
|---|---|
| Operating Voltage | 475-600 VAC |
| Power Consumption | 4.5W at 600V |
| Auto Ranges | No |
| Monitored Conditions | Phase Loss, Phase Reversal, Over/Under Voltage and Voltage Unbalance |
| Frequency | 50/60Hz |
| Type of Measurement | RMS |
| Under Voltage Trip | 90% ±1% (% of setpoint) |
| Under Voltage Reset | 93% ±1% (% of setpoint) |
| Over Voltage Trip | 110% ±1% (% of setpoint) |
| Over Voltage Reset | 107% ±1% (% of setpoint) |
| Voltage Unbalance Trip | 2-8%, adjustable (conforms to NEMA) |
| Voltage Unbalance Reset | Trip setting minus 0.7% |
| Trip Delay Time (Over, Under, & Unbalanced) | 1-30 sec., adjustable |
| Trip Delay Time (Single-Phasing Faults) | 1 sec., fixed |
| Trip Delay Time (Unbalance > 15%) | 1 sec., fixed |
| Restart Delay | Disabled in manual reset mode |
| Manual Reset Input | 5V open circuit/500µA short circuit |
| Manual Reset Requirement | External N.O. momentary pushbutton required for manual reset |
| Output Contacts | 1x N.C., 1x N.O. 7.5A at 240VAC resistive |
| Operating Temperature | -20° to +140° F |
| Humidity Tolerance | 0-97% w/o condensation |
| Terminal Torque | 3.5 in. lbs. maximum |
| Wire Type | Stranded or solid 14-26 AWG, 1/terminal |
| Enclosure Material | Noryl plastic |
| Mounting | DIN Rail or Surface Mount |
| Additional Options | /SG = Silver with Gold Flash Contacts |
| Warranty | 5-year Unconditional Warranty |