Current Unbalance Detector

The Model 2722 Current Unbalance Detector provides essential monitoring for 3-phase AC current systems. This device compares three single-phase motors and detects open 3-phase heating elements, preventing potential equipment damage and operational inefficiencies. With an input voltage range of 190-250VAC and a frequency range of 50-400Hz, it offers broad applicability across various industrial setups. Its robust design includes 2500V transient protection for 10ms, ensuring system integrity against electrical disturbances. The unit features an adjustable unbalance detection from 2% to 25% and a configurable trip delay from 0.2 to 20 seconds, allowing precise system integration and response customization. Operating reliably from -20° to +131° F with 0-97% humidity tolerance, the Model 2722 maintains consistent performance in diverse industrial environments, contributing to sustained operational uptime.

Ph Unbal Detector

DOWNLOADS:

c2722-220vac

Specifications

Input Voltage240VAC
Input Voltage Range190-250VAC
Power Consumption1.5W
VA Burden0.5VA per phase
Frequency Range50 - 400Hz
Current Range1 - 5 amps AC
Transient Protection2500V for 10ms
Unbalance Adjustment2% to 25%
Trip Delay0.2 to 20 seconds ± 5%
Output Contact FormDPDT
Output Contact Rating10A at 240VAC resistive
Expected Relay Life (Mechanical)10 million operations
Expected Relay Life (Electrical)100,000 at rated load
Operating Temperature-20° to +131° F
Humidity Tolerance0-97% w/o condensation
Enclosure MaterialABS plastic
Agency ApprovalUL Recognized
Agency ApprovalCSA Certified
FunctionMonitors 3-phase AC Current
FunctionCompares Three Single-phase Motors
FunctionDetects Open 3-phase Heating Element
Reset TypeAutomatic or Manual Reset

FAQs

What are the primary electrical input specifications for the Model 2722 Current Unbalance Detector?
The Model 2722 operates with an input voltage of 240VAC, within a range of 190-250VAC. It monitors current in the 1-5 amps AC range.
How are unbalance detection and trip delay configured on this device?
Unbalance detection is adjustable from 2% to 25%. The trip delay can be set between 0.2 and 20 seconds, with a tolerance of ±5%.
What are the output contact ratings and environmental operating conditions for the Model 2722?
The output contacts are DPDT, rated for 10A at 240VAC resistive. The device functions within an operating temperature range of -20° to +131° F and tolerates 0-97% humidity without condensation.