3-Phase Current Unbalance Detector

272-120

The MODEL 272 3-Phase Current Unbalance Detector, SKU 272-120, provides essential protection for three-phase systems. This device monitors current balance, preventing equipment damage from phase loss or voltage unbalance. Its adjustable unbalance trip point, ranging from 2% to 25%, allows for precise application tailoring. A configurable trip delay, from 0.5 to 10 seconds, helps mitigate nuisance trips while ensuring timely response to critical conditions. Operating reliably from -20° to +131° F, it integrates seamlessly into diverse industrial environments. The unit's automatic reset feature simplifies system recovery after a fault. With a contact rating of SPDT 10A at 240VAC resistive, it offers robust control. This detector contributes to extended motor life and reduced downtime by proactively identifying and addressing current imbalances, enhancing overall system longevity and operational efficiency.

3Ph Current Unbal Mon

DOWNLOADS:

272-120

Specifications

Input Voltage115VAC
Input Voltage Range100-130VAC
Power Consumption1.5W
VA Burden0.5VA per phase
Frequency Range50-400Hz
Current Range1 - 5 amps AC
Input Current40 amps for 2 seconds
Unbalance Adjustment2% to 25%
Trip Delay0.5 to 10 seconds ± 20%
Contact RatingSPDT 10A at 240VAC resistive
Expected Relay Life (Mechanical)10 million operations
Expected Relay Life (Electrical)100,000 at rated load
Transient Protection2500V for 10ms
Operating Temperature-20° to +131° F
Humidity Tolerance0-97% w/o condensation
Enclosure MaterialABS plastic
Reset TypeAutomatic Reset

FAQs

What is the operating voltage and current range for the 272-120 detector?
The 272-120 operates on 115VAC with an input voltage range of 100-130VAC. It monitors current within a 1 to 5 amps AC range.
How can the unbalance detection sensitivity be adjusted on this unit?
The unbalance adjustment on the 272-120 can be set from 2% to 25%, allowing for customization based on specific application requirements.
What is the expected lifespan of the relay contacts in the 272-120?
The relay contacts have an expected mechanical life of 10 million operations and an electrical life of 100,000 operations at rated load.