Model 19 3-Phase Monitor with Trip & Restart Delays

19-120

The Model 19 3-Phase Monitor provides essential protection for industrial systems. It continuously monitors for phase loss, low voltage, and phase reversal, ensuring operational integrity. With an automatic reset function, the unit streamlines system recovery following detected anomalies. Users can configure trip delays from 1 to 30 seconds and restart delays from 1 to 300 seconds, allowing for precise control over equipment response and preventing premature restarts. This monitor is compatible with both Wye and Delta systems and does not require a neutral connection, simplifying installation procedures. Its robust design includes transient protection up to 2500VAC for 10ms, contributing to reliable performance in demanding environments. Output contacts are rated SPDT 10 amps at 240VAC resistive, suitable for various control applications. The unit operates reliably across a -20° to +131° F temperature range, maintaining a repeat accuracy of ± 0.1% of the set point under fixed conditions.

3Ph Adj Trp/Rstrt Dly

DOWNLOADS:

19-120

Specifications

DetectionPhase loss, low voltage, phase reversal
Reset TypeAutomatic
WarrantyFive year unconditional
Nominal AC (phase to phase)120VAC
Adjustment range85-120VAC
Frequency60Hz
Power consumption1.4W
Transient protection2500VAC for 10ms
Repeat accuracy± 0.1% of set point (fixed conditions)
Trip delay1-30 sec.
Restart Delay1-300 sec.
Dead bandApproximately 2%
Output contactsSPDT 10 amps at 240VAC resistive
Expected relay life (Mechanical)10 million operations
Expected relay life (Electrical)100,000 operations at rated load
Operating temp-20° to +131° F
Humidity tolerance0-97% w/o condensation
Enclosure materialNORYL plastic cover; 6/6 Nylon base
Mounting8-pin socket (**sold separately)
Accessory SocketOrder 8-pin socket number 51X120
System CompatibilityWye or Delta systems
Neutral ConnectionNot required
IndicatorsFAULT and NORM condition indicators

FAQs

What types of electrical faults does the Model 19 monitor detect?
The Model 19 3-Phase Monitor detects phase loss, low voltage, and phase reversal conditions.
What are the adjustable delay ranges for the trip and restart functions?
The trip delay is adjustable from 1 to 30 seconds, and the restart delay is adjustable from 1 to 300 seconds.
What are the output contact specifications for this monitor?
The output contacts are SPDT 10 amps at 240VAC resistive.