Current Sensitive Relay

The Model 2734 Current Sensitive Relay offers precise current monitoring essential for industrial control systems. Its configurable operating voltage, supporting both 24VAC and 120VAC, provides installation flexibility across various power infrastructures. Users can adjust the over-current range from 0.5 to 20 amps by varying current transformer passes, accommodating diverse load requirements with accuracy. The device features a user-selectable reset function, allowing for either automatic or manual operation, which enhances system control and fault recovery procedures. With a robust 10A at 240VAC resistive contact rating and a trip delay adjustable from 0.2 to 2.5 seconds, the 2734 ensures reliable circuit protection and operational stability. Its durable ABS plastic enclosure contributes to its longevity in demanding operational environments, maintaining performance across an operating temperature range of +32° to +140° F. This relay is engineered for consistent, dependable service.

Current Sensitive Relay

DOWNLOADS:

2734

Specifications

Config: Operating Voltage24VAC, 120VAC
Voltage Range (for 24VAC)21-30VAC
Voltage Range (for 120VAC)100-140VAC
Power Consumption (for 24VAC)0.5W
Power Consumption (for 120VAC)2.0W
Frequency60Hz
Over-current Range (1 pass thru CT)2-20 amps
Over-current Range (2 passes thru CT)1-10 amps
Over-current Range (4 passes thru CT)0.5-5 amps
CT Insulation Rating600VAC
Dead Band± 1% of trip setting
Trip Point Repeatability± 2% of trip point
Trip Delay0.2 to 2.5 seconds
Start-up Delay0.5 to 6 seconds
ResetUser selectable - Auto or Manual
Contact ConfigurationSPDT
Contact Rating10A at 240VAC resistive
Expected Relay Life (Mechanical)10 million operations
Expected Relay Life (Electrical)100,000 operations at rated load
Operating Temperature+32° to +140° F
Humidity Tolerance0-97% without condensation
Enclosure MaterialABS plastic

FAQs

What operating voltages does the Model 2734 Current Sensitive Relay support, and what is its power consumption?
The Model 2734 supports 24VAC (21-30VAC range) with 0.5W power consumption and 120VAC (100-140VAC range) with 2.0W power consumption.
How can the over-current detection range be adjusted on the Model 2734?
The over-current range is adjustable by varying current transformer passes. It detects 2-20 amps with one pass, 1-10 amps with two passes, and 0.5-5 amps with four passes.
What are the delay and reset options available for the Model 2734 Current Sensitive Relay?
The Model 2734 features an adjustable trip delay from 0.2 to 2.5 seconds and a start-up delay from 0.5 to 6 seconds. Reset is user-selectable for either automatic or manual operation.