Model 2644 3-Phase Monitor

The Model 2644 3-Phase Monitor provides essential protection for industrial systems. Operating at 380VAC with a 50Hz frequency, this device detects critical conditions including phase loss, low voltage, and phase reversal. Its restart delay feature, approximately 3.5 minutes, ensures controlled system recovery after a fault. Users can adjust the response time from 0.2 to 20 seconds, allowing for application-specific tuning to prevent nuisance tripping. The monitor features DPDT 10 amp output contacts at 240VAC resistive, ensuring reliable switching for control circuits. With a robust design, including an ABS plastic enclosure and a 5-year unconditional warranty, the Model 2644 offers consistent performance across an operating temperature range of -20° to +131° F. UL Recognized and CSA Certified, it meets stringent industry standards for dependable operation in diverse environments, minimizing downtime.

3Ph Pwr Mon

DOWNLOADS:

ex2644r-380v

Specifications

Reset TypeRestart Delay
Restart Delay Timeapproximately 3.5 minutes
Nominal AC Voltage380VAC (phase to phase)
Adjustment Range300-400V
Frequency50Hz
Power Consumption4.5W
FunctionDetects Phase Loss, Low Voltage and Phase Reversal
Warranty5 Year Unconditional Warranty
Transient Protection2500 VRMS for 10ms
Repeat Accuracy± 0.1% of setpoint (fixed conditions)
Response TimeAdjustable 0.2 to 20 seconds ±10%
Dead BandApproximately 2%
Output ContactsDPDT 10 amps at 240VAC resistive
Expected Relay Life, Mechanical10 million operations
Expected Relay Life, Electrical100,000 operations at rated load
Operating Temperature-20° to +131° F
Humidity Tolerance0-97% w/o condensation
Enclosure MaterialABS plastic
MountingSurface
Agency ApprovalsUL Recognized and CSA Certified

FAQs

What types of phase conditions does the Model 2644 monitor detect?
The Model 2644 3-Phase Monitor detects phase loss, low voltage, and phase reversal.
What is the restart delay time for the Model 2644?
The Model 2644 features a restart delay time of approximately 3.5 minutes.
What are the nominal voltage and frequency specifications for this monitor?
The Model 2644 operates at a nominal AC voltage of 380VAC (phase to phase) and a frequency of 50Hz, with an adjustment range of 300-400V.