True RMS Current Monitor
The Model 27 True RMS Current Monitor provides precise current measurement and control for industrial applications. Its True RMS sensing capability ensures accurate readings across various waveforms, critical for maintaining system integrity. With an input range extending from 0.5A to 1200A via external CTs, it accommodates diverse system requirements, from low-current detection to high-current protection. Users can configure high and low trip delays from 0 to 20 seconds, along with adjustable hysteresis from 1 to 15%, providing tailored protection against overcurrent or undercurrent conditions. The unit supports both automatic and manual restart options, enhancing operational flexibility and minimizing downtime. Its robust design, featuring a Lexan 920 Polycarbonate enclosure and DIN Rail mounting, ensures reliable performance in demanding industrial environments. This monitor delivers essential data and control for optimized system operation.
1Ph Current Monitor
Specifications
| Input AC Current Range | 0.5A - 1200A with External CT |
|---|---|
| Input AC Current Range (at Terminals) | 0.5A - 5A at Terminals |
| Input Amps | 5A |
| Input Frequency | 50/60Hz (400Hz optional with jumper) |
| Input DC Power | 24 Volts, 2 watts |
| Output Rating (Resistive) | 240V AC, 10A |
| Output Rating (General Use) | 120V AC, 4A |
| Output Rating (General Use) | 240V AC, 2A |
| Output Rating (Pilot Duty) | C300 |
| Max Voltage on Current Terminals | 600V |
| Start-up Delay | 5 secs. Min. or Automatic reset delay setting (to allow for solid lock) |
| Output Contacts | SPDT x 2 10 Amps @ 240VAC |
| Repeat Accuracy | ± 0.5% (fixed conditions) |
| Reset Type | Manual or Automatic |
| Expected Relay Life (Mechanical) | 10 million operations |
| Expected Relay Life (Electrical) | 100,000 min. at rated load |
| Operating Temperature | -20°F to +130°F |
| Humidity Tolerance | 0-97% w/o condensation |
| Enclosure Material | Lexan 920 Polycarbonate UL 94 V-0 1.5 mm UL E45329 |
| Mounting | DIN Rail 35mm |
| Display Accuracy | +/- 0.5% |
| Display Update Rate | updated every second and re-initialized every 30 seconds |
| Config: High current | Enable/Disable |
| Config: High current Set Range | Low Set + 1% to 1200A in 0.5A steps |
| Config: High trip delay | 0 to 20.0 seconds in 0.1Sec steps |
| Config: Low current | Enable/Disable |
| Config: Low current Set Range | 1A to High Set -1% in 0.5A steps |
| Config: Low trip delay | 0 to 20.0 seconds in 0.1Sec steps |
| Config: Relay operation | Current High/Low option, Separate High/Low relays, DPDT, Other faults DPDT |
| Config: Relay operation on fault | De-energize on fault, Energize on fault |
| Config: High/Low Hysteresis range | As a % of set point 1 to 15% in 1% increments |
| Config: External CT ratio | 5:5 to 1200:5 |
| Config: Start-up delay | 2 to 15 seconds |
| Config: Restart | Automatic or Manual |
| Config: High or No High Restart when Automatic | High Restart, No High Restart |
| Config: Automatic Restart Delay range | 1 to 300 Minutes in 1 Minute steps |