True RMS Voltage Monitor

26

The MODEL 26 True RMS Voltage Monitor provides precise voltage monitoring for industrial applications. Its 80-550 VAC input range accommodates diverse system requirements, ensuring broad compatibility. Users can configure high and low voltage set points, along with adjustable trip delays, to suit specific operational parameters. The device offers user-selectable relay operation options, including HI-LO or DPDT, and fault energization choices, enhancing system flexibility. With a robust Lexan 920 polycarbonate enclosure and a UL 94 V-0 flammability rating, it ensures durability and safety. DIN Rail 35mm mounting simplifies installation and integration into existing panels. This monitor delivers reliable performance for critical voltage supervision tasks, contributing to system stability and protection. Its design prioritizes functional adaptability and consistent operation in demanding industrial environments, minimizing downtime.

1Ph Voltage Monitor

DOWNLOADS:

26

Specifications

Input Voltage (VAC)80-550 Volts
Input Current1mA
Input Frequency50/60Hz (400Hz optional with jumper)
DC Power24 Volts, 2 watts
Output Rating (Resistive)240V AC, 10A
Output Rating (General Use)120V AC, 4A
Output Rating (General Use)240V AC, 2A
Output Rating (Pilot Duty)C300, Pilot Duty
Start-up Delay5 secs. Min. or Automatic reset delay setting (to allow for solid lock)
Output ContactsSPDT x 2 10 Amps @ 240VAC
Repeat Accuracy± 0.5% (fixed conditions)
Reset TypeManual or Automatic
Expected Relay Life (Mechanical)10 million operations
Expected Relay Life (Electrical)100,000 min. at rated load
Operating Temperature-20°F to +130°F
Humidity Tolerance0-97% w/o condensation
Enclosure MaterialLexan 920, Polycarbonate
Enclosure Flammability RatingUL 94 V-0 1.5 mm
MountingDIN Rail 35mm
Display Accuracy+/- 0.5%
Relay Operation OptionsUser selectable High-Low or DPDT
Fault Energization OptionsEnergize on fault or de-energize on fault
High Voltage Setting (Factory Default)Enabled, Set point = 550V, Delay = 5S
High Voltage Set Point RangeLow setpoint + 1% to 550V in 0.5V steps
High Trip Delay Range0 to 20.0 seconds in 0.1Sec steps
Low Voltage Setting (Factory Default)Enabled, Set point = 80V, Delay = 5S
Low Voltage Set Point Range80 to High Setpoint -1% in 0.5V steps
Low Trip Delay Range0 to 20.0 seconds in 0.1Sec steps
Relay Operation (Factory Default)HI-LO
Relay Operation on Fault (Factory Default)De-energize on fault
Restart (Factory Default)Automatic
Automatic Restart Delay Range (Factory Default)5S
Automatic Restart Delay Range0 to 300.0 Seconds in 0.1Sec steps

FAQs

What is the operational input voltage range for the MODEL 26 True RMS Voltage Monitor?
The MODEL 26 accepts an input voltage range of 80-550 Volts AC.
What are the output contact specifications for this voltage monitor?
The device features two SPDT output contacts, each rated at 10 Amps at 240VAC.
What is the specified operating temperature range for the MODEL 26?
The MODEL 26 is designed to operate reliably within a temperature range of -20°F to +130°F.