3-Phase Monitor with Adjustable Trip & Restart Delays

22M

The 22M 3-Phase Monitor provides essential protection for industrial electrical systems. Its adjustable trip delay, ranging from 1 to 30 seconds, allows for precise fault response tailored to specific equipment requirements. A configurable restart delay, from 1 to 500 seconds, prevents immediate re-energization, safeguarding machinery from rapid cycling. Operating across a 190-480 VAC range at 50/60Hz, this monitor accommodates diverse power infrastructures. It features 2X SPDT 10A output contacts for reliable control integration. The unit's manual reset capability ensures controlled system restoration after an event. It monitors for under voltage (90% ±1% trip), over voltage (110% ±1% trip), and voltage unbalance (2-8% adjustable trip) using RMS measurement. This device offers robust monitoring capabilities for critical applications, ensuring operational continuity and equipment longevity.

Dpdt 480V Universal 3-Ph M

DOWNLOADS:

22m

Specifications

Reset TypeManual Reset
Operating Voltage190-480 VAC
Power Consumption6W at 480V
Auto RangesYes
Frequency50/60Hz
Type of MeasurementRMS
Under Voltage Trip90% ±1% (% of setpoint)
Under Voltage Reset93% ±1% (% of setpoint)
Over Voltage Trip110% ±1% (% of setpoint)
Over Voltage Reset107% ±1% (% of setpoint)
Voltage Unbalance Trip2-8%, adjustable (conforms to NEMA)
Voltage Unbalance ResetTrip setting minus 0.7%
Trip Delay (Voltage/Unbalance Faults)1-30 sec., adjustable
Trip Delay (Single-Phasing Faults)1 sec., fixed
Trip Delay (Unbalance > 15%)1 sec., fixed
Restart Delay1-500 sec., adjustable
Manual Reset Input5V open circuit/500µA short circuit
Manual Reset RequirementExternal N.O. momentary pushbutton required
Output Contacts2X SPDT 10A at 240VAC resistive
Operating Temperature-20° to +140° F
Humidity Tolerance0-97% w/o condensation
Terminal Torque (Power and Relay)9 in lbs max
Terminal Torque (Manual Reset)5.3 in lbs max
Wire Type (Power and Relay)12-22 AWG
Wire Type (Manual Reset)12-30 AWG
EnclosureNoryl plastic
MountingSurface Mount
Additional Options/SG = Silver with Gold Flash Contacts
System CompatibilityWye or Delta systems
Neutral ConnectionNot required
Dimension Tolerance± 0.06 in
Mounting Hole Diameter0.25 in
Warranty5-year Unconditional Warranty

FAQs

What is the operating voltage range for the 22M 3-Phase Monitor?
The 22M operates within a 190-480 VAC range.
What are the adjustable delay ranges for trip and restart functions?
The trip delay is adjustable from 1-30 seconds, and the restart delay is adjustable from 1-500 seconds.
What type of output contacts does the 22M monitor utilize?
It utilizes 2X SPDT 10A at 240VAC resistive output contacts.