The Model 19 3-Phase Monitor offers essential protection for industrial systems. It accurately detects phase loss, low voltage, and phase reversal, safeguarding connected equipment from operational disruptions. With an automatic reset type, the unit minimizes downtime by restoring power once conditions stabilize. Users can configure precise operational parameters through adjustable trip delays, ranging from 1 to 30 seconds, and restart delays, from 1 to 300 seconds. This flexibility allows for tailored system response to varying load conditions. The monitor is compatible with both Wye and Delta systems, requiring no neutral connection for simplified integration. Its robust design, featuring SPDT 10 amp output contacts and a five-year unconditional warranty, ensures consistent performance and reliability in demanding operational environments. Power consumption is 1.4W.

3Ph Adj Trp/Rstrt Dly

DOWNLOADS:

19-480-400

Specifications

DetectionPhase loss, low voltage, phase reversal
Reset TypeAutomatic
WarrantyFive year unconditional
Nominal AC (phase to phase)120VAC
Adjustment range85-120VAC
Frequency400Hz
Power consumption1.4W
Transient protection2500VAC for 10ms
Repeat accuracy± 0.1% of set point (fixed conditions)
Trip delay1-30 sec.
Restart Delay1-300 sec.
Dead bandApproximately 2%
Output contactsSPDT 10 amps at 240VAC resistive
Expected relay life (Mechanical)10 million operations
Expected relay life (Electrical)100,000 operations at rated load
Operating temp-20° to +131° F
Humidity tolerance0-97% w/o condensation
Enclosure materialNORYL plastic cover; 6/6 Nylon base
Mounting8-pin socket (**sold separately)
Accessory SocketOrder 8-pin socket number 51X120
System CompatibilityWye or Delta systems
Neutral ConnectionNot required
IndicatorsFAULT and NORM condition indicators

FAQs

What types of electrical anomalies does the Model 19 monitor detect?
The Model 19 3-Phase Monitor detects phase loss, low voltage, and phase reversal conditions within a system.
What are the adjustable delay ranges for the trip and restart functions?
The trip delay is adjustable from 1 to 30 seconds, and the restart delay can be set from 1 to 300 seconds.
What are the output contact specifications and system compatibility of this monitor?
The output contacts are SPDT 10 amps at 240VAC resistive. This monitor is compatible with both Wye and Delta electrical systems.