The EX269R Over & Under 3-Phase Monitor offers essential protection for industrial electrical systems. This device monitors critical conditions including high voltage, low voltage, phase loss, and phase reversal, ensuring operational integrity. With a nominal AC voltage of 380VAC and adjustable upper/lower ranges (350-450V and 300-400V respectively), it adapts to specific system requirements. Its 50Hz frequency compatibility and 6W power consumption demonstrate efficient integration. The monitor features a fixed response time of 4 ±2 seconds and an adjustable reset time from 0.3 to 5 minutes, allowing for tailored system recovery. Output contacts are SPDT 10A at 240VAC resistive, providing reliable control for connected equipment. Designed for consistent performance, it operates within a -20° to +130° F temperature range and tolerates 0-97% humidity without condensation. Its 10 million mechanical operations relay life ensures long-term durability.

Volt Mon W/Restart Dly

DOWNLOADS:

ex269r

Specifications

Monitored ConditionsHigh Voltage, Low Voltage, Phase Loss & Phase Reversal
Nominal AC Voltage (phase to phase)380VAC
Adjustable Range - Upper350-450V
Adjustable Range - Lower300-400V
Frequency50Hz
Power Consumption6W
Transient Protection2500VRMS for 10ms
Repeat Accuracy± 0.1% of set point (fixed conditions)
Response Time4 ±2 seconds fixed
Reset TimeAdjustable 0.3 to 5 minutes
Reset TypeAutomatic
Dead BandApproximately 2%
Output ContactsSPDT 10A at 240VAC resistive
Expected Relay Life (Mechanical)10 million operations
Expected Relay Life (Electrical)100,000 operations at rated load
Operating Temperature-20° to +130° F
Humidity Tolerance0-97% w/o condensation
Enclosure MaterialABS Plastic
MountingSurface
Warranty5 Year Unconditional Warranty

FAQs

What specific electrical conditions does the EX269R monitor
The EX269R monitors high voltage, low voltage, phase loss, and phase reversal in 3-phase systems.
What are the adjustable voltage ranges for the EX269R
The adjustable upper voltage range is 350-450V, and the adjustable lower voltage range is 300-400V for a nominal 380VAC system.
What is the reset time capability of the EX269R monitor
The EX269R features an adjustable reset time ranging from 0.3 to 5 minutes, with an automatic reset type.