EX259-380VAC
The MODEL 259 3-Phase Monitor, SKU EX259, provides essential protection for industrial systems. This device features adjustable trip and restart delays, allowing for precise control over operational parameters. Its adjustable voltage level accommodates diverse application requirements, operating nominally at 380VAC with a 300-400VAC range. With DPDT 600VAC output contacts, it ensures reliable switching capabilities for critical loads. The monitor offers robust transient protection of 2500V for 10ms, safeguarding connected equipment from electrical disturbances. Operating efficiently across a -20° to +131° F temperature range and tolerating 0-97% humidity without condensation, it maintains consistent performance in challenging industrial environments. The unit's 5-year unconditional warranty underscores its design for sustained utility and operational longevity. Its repeat accuracy of ± 0.1% ensures consistent monitoring.
The Model 259 3-Phase Monitor is designed to protect individual 3-phase
equipment and motors, or in conjunction with shunt trip breakers. When
correct voltage and phase rotation is applied, an internal DPDT relay
energizes. A fault condition (phase loss, phase reversal, or low
voltage) drops out the relay and lights the LED failure indicator. The
Model 259 will detect a phase loss condition even when regenerative
voltage is present. The Model 259 may be used with Wye or Delta
systems and requires no neutral connection. Standard operating ranges
are available from 120 to 575 VAC, 60Hz and 380 VAC, 50Hz
Out of stock
$706.00
Specifications
| Output Contacts | DPDT 600VAC |
|---|---|
| Trip & Restart Delays | Adjustable |
| Voltage Level | Adjustable |
| Warranty | 5 Year Unconditional |
| Nominal AC Voltage (phase to phase) | 380VAC |
| Adjust Range (VAC) | 300-400 |
| Frequency | 50Hz |
| Power Consumption | 4.2W |
| Transient Protection | 2500V for 10ms |
| Repeat Accuracy | ± 0.1% (fixed conditions) |
| Response Time | Adjustable 1 to 5 seconds |
| Reset Time | Adjustable 0.2 to 10 minutes |
| Reset Type | Automatic |
| Dead Band | Approximately 2% |
| Output Contacts Type | DPDT |
| Output Contact Rating | 3A at 480/600VAC, 80% PF |
| Output Contact Rating | 10A at 240VAC, 80% PF resistive |
| Expected Relay Life (Mechanical) | 10 million operations |
| Expected Relay Life (Electrical) | 100,000 operations at rated load |
| Operating Temperature | -20° to +131° F |
| Humidity Tolerance | 0-97% w/o condensation |
| Enclosure Material | 20 gauge steel |
| Mounting | Surface |