3-Phase Monitor

EX246-380VAC

The EX246 3-Phase Monitor offers essential protection for industrial electrical systems. This device continuously monitors for critical conditions including phase loss, phase reversal, low voltage, and over voltage, ensuring operational integrity. Its automatic reset functionality minimizes downtime by restoring operation without manual intervention once faults clear. With a robust 5-year unconditional warranty and a mechanical relay life of 10 million operations, the EX246 provides long-term reliability. Precise monitoring is maintained with a repeat accuracy of ±0.1% of the set point and a rapid 50ms response time. This unit is designed for consistent performance in demanding environments, operating from -20° to +131° F with 0-97% humidity tolerance. Its SPDT 10A contact rating at 240VAC resistive ensures reliable switching for various control applications. The compact design and ABS plastic enclosure contribute to its utility in diverse industrial settings.

3Ph Pwr Mon

DOWNLOADS:

ex246-380vac

Specifications

Monitors forPhase Loss or Reversal, Low and Over Voltage
Reset TypeAutomatic
Warranty5 Year Unconditional Warranty
Nominal AC Voltage380
Adjustment Range (Low)300-400 V
Adjustment Range (High)350-450 V
Frequency50Hz
Power Consumption (per phase)2W
Transient Protection2500V for 10ms
Repeat Accuracy±0.1% of set point (fixed conditions)
Response/Reset Time50ms
Dead Band2%
Contact RatingSPDT 10A at 240VAC resistive
Expected Relay Life (Mechanical)10 million operations
Expected Relay Life (Electrical)100,000 at rated load
Operating Temperature-20° to +131° F
Humidity Tolerance0-97% w/o condensation
Enclosure MaterialABS plastic
Mounting8-pin socket *order separately
Max Input Voltage450VAC

FAQs

What electrical conditions does the EX246 3-Phase Monitor detect?
The EX246 monitors for phase loss, phase reversal, low voltage, and over voltage conditions in a 3-phase system.
What are the adjustable voltage ranges for the EX246 monitor?
For a nominal 380V AC system, the low voltage adjustment range is 300-400V, and the high voltage adjustment range is 350-450V.
What are the environmental operating limits for the EX246 3-Phase Monitor?
The EX246 operates within a temperature range of -20° to +131° F and tolerates 0-97% humidity without condensation.