EX200-380V
The Model 200 3-Phase Voltage Unbalance Monitor (EX200) provides essential protection for industrial equipment. It precisely monitors 380VAC, 50Hz systems, detecting voltage unbalance between 2% and 10%. A rapid 100ms response time ensures prompt action against potentially damaging conditions. Its DPDT 10 amp contacts at 240VAC resistive facilitate reliable control. The unit operates effectively across a wide temperature range from -20° to +131° F, maintaining performance in diverse environments. This monitor contributes to extended machinery lifespan by mitigating risks associated with voltage irregularities, offering consistent operational stability. The automatic reset feature simplifies system recovery after fault conditions. With a repeat accuracy of ± 0.1%, the Model 200 delivers consistent monitoring performance. Its robust ABS plastic enclosure and transient protection up to 2500VRMS for 10ms enhance durability in demanding industrial settings.
The Model 200 3-Phase Voltage Unbalance Monitor is designed to
continuously monitor a three-phase line for unbalanced voltage
conditions. This device will only energize the relay if an unbalance
exists. Zero volts on all three phases is considered a balanced
condition. This allows the Model 200 to be used with shunt breakers, so
that the breaker can shut off the main power without tripping the
monitor. The solid-state sensing circuit drives an internal
electromechanical relay. Indicator lights on the monitor show when the
voltage balance is within an acceptable range; when an unbalance exists;
and when the relay is actually tripped. When an acceptable voltage
balance is reapplied, the Model 200 will automatically reset the relay.
Out of stock
$468.00
Specifications
| Nominal AC Voltages | 380VAC |
|---|---|
| Voltage Range | ± 15% |
| Frequency | 50Hz |
| Power Consumption (per phase) | 2W |
| Transient Protection | 2500VRMS for 10ms |
| Repeat Accuracy | ± 0.1% (fixed conditions) |
| Unbalance Adjustment | 2% to 10% |
| Response Time | 100ms |
| Reset Time | Fixed 1 sec |
| Dropout Time | Adjustable 0.2 to 20 seconds |
| Reset Type | Automatic |
| Dead Band | 0.5% max |
| Contact Rating | DPDT 10 amps at 240VAC resistive |
| Expected Relay Life (Mechanical) | 10 million operations |
| Expected Relay Life (Electrical) | 100,000 operations at rated load |
| Operating Temp | -20° to +131° F |
| Humidity Tolerance | 0-97% w/o condensation |
| Mounting | Surface |
| Enclosure Material | ABS plastic |
| Mounting Hole Diameter | 0.19 |