DC260B20-24
The DC260B-20-24 Voltage Sensor offers reliable DC voltage monitoring for industrial applications. Its automatic reset function simplifies system management, while the 20-24VDC input range accommodates common control circuits. With a rapid 100ms response time, it quickly detects voltage deviations, enabling timely system adjustments. The sensor's continuous duty operation ensures consistent performance in demanding environments. UL Recognized and CSA Certified, this device meets stringent safety and performance standards. Its robust design includes transient protection up to 2500 VRMS for 10ms and a wide operating temperature range of -20° to +131° F. The SPDT 10 Amp output contacts provide versatile control capabilities. This sensor is engineered for durability, featuring an electrical relay life of 100,000 operations at rated load, contributing to extended operational uptime.
The Model 260 Voltage Sensor is a single set-point voltage sensor. Input
voltages above the set-point cause the output contacts to energize
(contacts 1 & 8 closed). Input voltages below the set-point cause
the output contacts to de-energize (contacts 1 & 2 closed). The dead
band between pull-in and drop-out is less than 2%. The standard unit
has a screwdriver, or fingertip adjustable set-point range of
approximately 35%. of the maximum voltage. This device can also be
provided with a factory calibrated trip point. AC versions of the
Model 260 Voltage Sensor are not frequency sensitive, and may be used in
systems from 50 Hz to 400 Hz. DC models are not polarity sensitive. This
device requires a standard 8-pin socket, such as Time Mark’s Model 51×120.
Out of stock
$148.00
Specifications
| Reset Type | Automatic |
|---|---|
| Voltage Type | DC |
| Input Voltage Range | 20-24 |
| Agency approval | UL Recognized and CSA Certified |
| Transient protection | 2500 VRMS for 10ms |
| Polarity protection | not required |
| Supply current | 10mA |
| Setpoint stability | ± 1% |
| Response time | 100ms |
| Operation | Continuous duty |
| Output contacts | SPDT 10 Amps at 240VAC resistive |
| Expected relay life (Mechanical) | 10 million operations |
| Expected relay life (Electrical) | 100,000 operations at rated load |
| Operating temperature | -20° to +131° F |
| Humidity tolerance | 0-97% without condensation |
| Enclosure material | ABS plastic |
| Mounting | 8-pin socket (**order separately) |
| Dead band | less than 2% |
| Polarity Sensitivity | not polarity sensitive |