3-Phase Monitor

The D2652 3-Phase Monitor provides essential protection for industrial equipment. This device safeguards against critical power anomalies including phase loss, low voltage, and phase reversal, which can lead to costly downtime and equipment damage. Its adjustable response time, ranging from 0.2 to 10 seconds, allows for precise system integration tailored to specific operational requirements. Operators can select either automatic or manual reset functionality, enhancing operational flexibility and control. With a nominal AC voltage of 575VAC and an adjustment range of 450-600V, the D2652 is suitable for diverse high-voltage applications. Its robust DPDT contact configuration and 10A at 240VAC resistive contact rating ensure reliable control circuit operation and extended mechanical life of 10 million operations. UL Recognized and CSA Certified, this monitor offers dependable performance in demanding industrial environments, minimizing risks associated with power fluctuations.

3Ph Power Mon

DOWNLOADS:

d2652-575vac

Specifications

Protection FunctionsDetects Phase Loss, Low Voltage and Phase Reversal
Nominal AC Voltage (phase to phase)575VAC
Adjustment Range450-600V
Frequency60Hz
Power Consumption (per phase)3W
Repeat Accuracy± 0.5% of set point (fixed conditions)
Response TimeAdjustable: 0.2 to 10 seconds ± 5%
Restart DelayAdjustable: 0.3 to 5 minutes ± 5%
Reset TypeSelectable: Automatic or Manual
Dead BandApproximately 2%
Contact ConfigurationDPDT
Contact Rating10A at 240VAC resistive
Mechanical Life10 million operations
Electrical Life100,000 operations at rated load
Operating Temperature-20° to +131° F
Humidity Tolerance0-97% w/o condensation
Enclosure MaterialABS plastic
MountingSurface
Agency ApprovalsUL Recognized and CSA Certified

FAQs

What specific power anomalies does the D2652 monitor protect against?
The D2652 detects phase loss, low voltage, and phase reversal to protect connected equipment.
What is the adjustable voltage range for the D2652 3-Phase Monitor?
The D2652 has an adjustment range of 450-600V for systems with a nominal AC voltage of 575VAC.
Can the D2652's response time and reset behavior be configured?
Yes, the response time is adjustable from 0.2 to 10 seconds, and the reset type is selectable as either automatic or manual.