The Model 2594 3-Phase Monitor provides essential protection for industrial systems. Designed for 575VAC nominal applications, its adjustable range of 450-600V accommodates diverse operational requirements. This unit ensures system integrity through features like 2500V transient protection for 10ms, safeguarding against voltage spikes. With a rapid 0.05-second response time and automatic reset, it minimizes downtime and maintains continuous operation. The DPDT 600VAC output contacts offer robust control capabilities, rated for 3A at 480/600VAC. Its durable construction supports an operating temperature range from -20° to +131° F and tolerates 0-97% humidity without condensation. Compatibility with both WYE and Delta systems enhances its versatility across various industrial setups, ensuring reliable performance and extended equipment life with a mechanical relay life of 10 million operations.

3Ph Pwr Mon

DOWNLOADS:

d2594-575vac

Specifications

Nominal AC Voltage (phase to phase)575VAC
Adjustment Range450-600
Frequency60Hz
Power Consumption6.9W
Output ContactsDPDT 600VAC
Failure LevelAdjustable
Reset TypeAutomatic
Warranty5 Year Unconditional
Transient Protection2500V for 10ms
Repeat Accuracy± 0.1% (fixed conditions)
Response Time0.05 seconds (fixed)
Reset Time0.05 seconds (fixed)
Output Contact Rating3A at 480/600VAC 80% PF
Output Contact Rating10A at 240VAC 80% PF resistive
Expected Relay Life (Mechanical)10 million operations
Expected Relay Life (Electrical)100,000 at rated load
Operating Temperature-20° to +131° F
Humidity Tolerance0-97% w/o condensation
Enclosure Material20 gauge steel
MountingSurface
System CompatibilityWYE or Delta systems

FAQs

What voltage systems is the D2594 3-Phase Monitor compatible with?
The D2594 is designed for 575VAC nominal phase-to-phase systems, with an adjustment range of 450-600V. It is compatible with both WYE and Delta system configurations.
What environmental conditions can the Model 2594 withstand?
This monitor operates reliably within a temperature range of -20° to +131° F. It also tolerates 0-97% humidity without condensation, ensuring performance in varied industrial environments.
What are the output contact specifications and reset behavior of the D2594?
The D2594 features DPDT 600VAC output contacts, rated for 3A at 480/600VAC. It incorporates an automatic reset type, providing continuous monitoring without manual intervention after a fault clears.