C265-480VAC
The Model 265 3-Phase Monitor, SKU C265, offers essential protection for industrial systems. This device continuously monitors for critical conditions including phase loss, low voltage, and phase reversal, ensuring operational integrity. With a nominal AC voltage of 480VAC and an adjustable range of 380-480V, it adapts to various applications. Its automatic reset type minimizes downtime, while a rapid 50ms maximum response time ensures swift detection of anomalies. The unit's robust SPDT 10 amp output contacts at 240VAC resistive provide reliable control. Designed for surface mounting, the C265 operates effectively across a -20° to +131° F temperature range, maintaining performance in demanding environments. Its 1.5W power consumption and 2500 VRMS transient protection contribute to its efficiency and durability.
The Model 265 3-Phase Monitor continuously monitors 3-phase Wye or Delta
systems for phase loss, low voltage and phase reversal. When properly
adjusted, the Model 265 Monitor will detect phase loss on a loaded motor
even when regenerated voltage is present. The solid-state sensing
circuit drives an internal relay, in a fail-safe configuration, i. e. ,
the relay is energized when correct voltage and phase rotation are
applied. Operating power for the Model 265 is drawn from the 3-phase
lines being monitored. An adjustable timer delays restarting of the
load, allowing up to five minutes for compressor head pressures to bleed
off, in the event of short-term power failures. The Model 265 Monitor
is not sensitive to line current, and can be used with any size motor or
compressor. Automatic and manual reset versions are available.
Out of stock
$346.00
Specifications
| Reset Type | Automatic |
|---|---|
| Monitored Parameters | Phase loss, low voltage, phase reversal |
| Nominal AC Voltage (phase to phase) | 480VAC |
| Adjustment Range | 380-480V |
| Frequency | 60Hz |
| Power Consumption | 1.5W |
| Transient Protection | 2500 VRMS for 10ms |
| Repeat Accuracy | ± 0.1% of set point (fixed conditions) |
| Response Time | 50ms maximum |
| Reset Time | Adjustable - 20 to 300 seconds ±10% |
| Dead Band | Approximately 2% |
| Output Contacts | SPDT 10 amps at 240VAC resistive |
| Expected Relay Life - Mechanical | 10 million operations |
| Expected Relay Life - Electrical | 100,000 operations at rated load |
| Operating Temperature | -20° to +131° F |
| Humidity Tolerance | 0-97% w/o condensation |
| Enclosure Material | ABS plastic |
| Mounting | Surface |
| Agency Approvals | UL Recognized and CSA Certified |