C265-480VAC

C265-480VAC

The Model 265 3-Phase Monitor, SKU C265, offers essential protection for industrial systems. This device continuously monitors for critical conditions including phase loss, low voltage, and phase reversal, ensuring operational integrity. With a nominal AC voltage of 480VAC and an adjustable range of 380-480V, it adapts to various applications. Its automatic reset type minimizes downtime, while a rapid 50ms maximum response time ensures swift detection of anomalies. The unit's robust SPDT 10 amp output contacts at 240VAC resistive provide reliable control. Designed for surface mounting, the C265 operates effectively across a -20° to +131° F temperature range, maintaining performance in demanding environments. Its 1.5W power consumption and 2500 VRMS transient protection contribute to its efficiency and durability.

The Model 265 3-Phase Monitor continuously monitors 3-phase Wye or Delta
systems for phase loss, low voltage and phase reversal. When properly
adjusted, the Model 265 Monitor will detect phase loss on a loaded motor
even when regenerated voltage is present. The solid-state sensing
circuit drives an internal relay, in a fail-safe configuration, i. e. ,
the relay is energized when correct voltage and phase rotation are
applied. Operating power for the Model 265 is drawn from the 3-phase
lines being monitored. An adjustable timer delays restarting of the
load, allowing up to five minutes for compressor head pressures to bleed
off, in the event of short-term power failures. The Model 265 Monitor
is not sensitive to line current, and can be used with any size motor or
compressor. Automatic and manual reset versions are available.

Out of stock

$346.00

Specifications

Reset TypeAutomatic
Monitored ParametersPhase loss, low voltage, phase reversal
Nominal AC Voltage (phase to phase)480VAC
Adjustment Range380-480V
Frequency60Hz
Power Consumption1.5W
Transient Protection2500 VRMS for 10ms
Repeat Accuracy± 0.1% of set point (fixed conditions)
Response Time50ms maximum
Reset TimeAdjustable - 20 to 300 seconds ±10%
Dead BandApproximately 2%
Output ContactsSPDT 10 amps at 240VAC resistive
Expected Relay Life - Mechanical10 million operations
Expected Relay Life - Electrical100,000 operations at rated load
Operating Temperature-20° to +131° F
Humidity Tolerance0-97% w/o condensation
Enclosure MaterialABS plastic
MountingSurface
Agency ApprovalsUL Recognized and CSA Certified

FAQs

What specific electrical conditions does the C265 3-Phase Monitor detect?
The C265 monitors for phase loss, low voltage, and phase reversal in 3-phase systems.
What is the nominal operating voltage and adjustment capability of this monitor?
The monitor operates at a nominal 480VAC (phase to phase) with an adjustable range from 380V to 480V.
Can you describe the output contact specifications and the reset mechanism?
It features SPDT 10 amp output contacts at 240VAC resistive. The reset type is automatic, with an adjustable reset time of 20 to 300 seconds.