C2644R-480V

C2644R-480V

The Model 2644 3-Phase Monitor provides essential protection for industrial systems. Operating at 480VAC with an adjustable range of 380-480V, this device safeguards equipment from critical power anomalies. It reliably detects phase loss, low voltage conditions, and phase reversal, preventing potential damage and operational downtime. Its restart delay feature, approximately 3.5 minutes, ensures controlled system re-engagement after a fault, contributing to system stability. With an adjustable response time from 0.2 to 20 seconds, the monitor can be precisely configured for specific application requirements, allowing for tailored protection. DPDT 10 amp output contacts offer robust control capabilities for various industrial loads. This unit's design prioritizes consistent system integrity and operational continuity, minimizing disruptions caused by electrical irregularities. Its 60Hz frequency compatibility and 4.5W power consumption ensure efficient integration into existing setups.

The Model 2644 3-Phase Monitor continuously monitors 3-phase Wye or
Delta systems for abnormal conditions. The solid-state electronic
sensing circuitry drives an internal DPDT relay, allowing the Model 2644
to operate two motor control circuits, or a control circuit and an alarm
circuit. An adjustable trip delay reduces or eliminates nuisance
tripping caused by momentary voltage fluctuations on motor start-up. An
optional restart delay gives approximately a 3.5-minute delay when the
relay drops out, to allow compressor head pressures to bleed off, in the
event of short-term power failures. Voltage adjustment ranges are
sufficiently wide to allow for proper calibration to existing
conditions. Both TRIP and NORM indicators are provided to aid in
adjustment and system troubleshooting. Automatic and manual reset
versions are available. The Model 2644 Monitor is not sensitive to line
current, and can be used with any size motor or compressor.

Out of stock

$338.00

Specifications

Reset TypeRestart Delay
Restart Delay Timeapproximately 3.5 minutes
Nominal AC Voltage480VAC (phase to phase)
Adjustment Range380-480V
Frequency60Hz
Power Consumption4.5W
FunctionDetects Phase Loss, Low Voltage and Phase Reversal
Warranty5 Year Unconditional Warranty
Transient Protection2500 VRMS for 10ms
Repeat Accuracy± 0.1% of setpoint (fixed conditions)
Response TimeAdjustable 0.2 to 20 seconds ±10%
Dead BandApproximately 2%
Output ContactsDPDT 10 amps at 240VAC resistive
Expected Relay Life, Mechanical10 million operations
Expected Relay Life, Electrical100,000 operations at rated load
Operating Temperature-20° to +131° F
Humidity Tolerance0-97% w/o condensation
Enclosure MaterialABS plastic
MountingSurface
Agency ApprovalsUL Recognized and CSA Certified

FAQs

What voltage ranges does the Model 2644 3-Phase Monitor support?
The Model 2644 operates at a nominal AC voltage of 480VAC (phase to phase) and has an adjustment range of 380-480V.
What types of electrical faults does the Model 2644 detect?
This monitor detects phase loss, low voltage conditions, and phase reversal to protect connected equipment.
How does the Model 2644 handle system restarts after a fault?
The Model 2644 features a restart delay reset type, with a delay time of approximately 3.5 minutes before re-engagement.
Select your currency
CAD Canadian dollar