C2644M-480VAC
The Model 2644 3-Phase Monitor provides essential protection for industrial equipment. Operating at 480VAC with an adjustment range of 380-480V, this device detects critical anomalies including phase loss, low voltage, and phase reversal. Its adjustable response time, from 0.2 to 20 seconds, allows for precise system integration. With DPDT 10 amp output contacts, it offers robust control capabilities. The unit features 2500 VRMS transient protection for 10ms, enhancing operational resilience against power disturbances. A repeat accuracy of ± 0.1% of setpoint ensures consistent performance under fixed conditions. Designed for surface mounting, its ABS plastic enclosure provides durability in industrial environments. With a 5-year unconditional warranty and UL Recognized and CSA Certified approvals, this monitor contributes to maintaining system uptime and preventing costly equipment damage through reliable phase monitoring.
The Model 2644 3-Phase Monitor continuously monitors 3-phase Wye or
Delta systems for abnormal conditions. The solid-state electronic
sensing circuitry drives an internal DPDT relay, allowing the Model 2644
to operate two motor control circuits, or a control circuit and an alarm
circuit. An adjustable trip delay reduces or eliminates nuisance
tripping caused by momentary voltage fluctuations on motor start-up. An
optional restart delay gives approximately a 3.5-minute delay when the
relay drops out, to allow compressor head pressures to bleed off, in the
event of short-term power failures. Voltage adjustment ranges are
sufficiently wide to allow for proper calibration to existing
conditions. Both TRIP and NORM indicators are provided to aid in
adjustment and system troubleshooting. Automatic and manual reset
versions are available. The Model 2644 Monitor is not sensitive to line
current, and can be used with any size motor or compressor.
Specifications
| Reset Type | Manual Reset |
|---|---|
| Nominal AC Voltage | 480VAC (phase to phase) |
| Adjustment Range | 380-480V |
| Frequency | 60Hz |
| Power Consumption | 4.5W |
| Function | Detects Phase Loss, Low Voltage and Phase Reversal |
| Warranty | 5 Year Unconditional Warranty |
| Transient Protection | 2500 VRMS for 10ms |
| Repeat Accuracy | ± 0.1% of setpoint (fixed conditions) |
| Response Time | Adjustable 0.2 to 20 seconds ±10% |
| Dead Band | Approximately 2% |
| Output Contacts | DPDT 10 amps at 240VAC resistive |
| Expected Relay Life, Mechanical | 10 million operations |
| Expected Relay Life, Electrical | 100,000 operations at rated load |
| Operating Temperature | -20° to +131° F |
| Humidity Tolerance | 0-97% w/o condensation |
| Enclosure Material | ABS plastic |
| Mounting | Surface |
| Agency Approvals | UL Recognized and CSA Certified |