3-Phase Monitor

C2594-480VAC

The Model 2594 3-Phase Monitor provides essential system protection for industrial operations. Designed for 480VAC nominal systems, it offers an adjustable range of 380-500V, ensuring adaptability across various applications. Its rapid 0.05-second response time and automatic reset capability minimize downtime by quickly addressing phase imbalances or failures. The unit features DPDT 600VAC output contacts and is compatible with both WYE and Delta systems. With a 5-year unconditional warranty, this monitor demonstrates robust construction and reliability. It operates effectively within a -20° to +131° F temperature range and tolerates 0-97% humidity without condensation. Transient protection is rated at 2500V for 10ms, enhancing durability. This device is engineered for consistent performance in demanding environments, safeguarding critical equipment through precise monitoring and stable operation.

3Ph Pwr Mon

DOWNLOADS:

c2594-480vac

Specifications

Nominal AC Voltage (phase to phase)480VAC
Adjustment Range380-500
Frequency60Hz
Power Consumption4.2W
Output ContactsDPDT 600VAC
Failure LevelAdjustable
Reset TypeAutomatic
Warranty5 Year Unconditional
Transient Protection2500V for 10ms
Repeat Accuracy± 0.1% (fixed conditions)
Response Time0.05 seconds (fixed)
Reset Time0.05 seconds (fixed)
Output Contact Rating3A at 480/600VAC 80% PF
Output Contact Rating10A at 240VAC 80% PF resistive
Expected Relay Life (Mechanical)10 million operations
Expected Relay Life (Electrical)100,000 at rated load
Operating Temperature-20° to +131° F
Humidity Tolerance0-97% w/o condensation
Enclosure Material20 gauge steel
MountingSurface
System CompatibilityWYE or Delta systems

FAQs

What voltage systems is the Model 2594 compatible with?
The Model 2594 is compatible with 480VAC nominal systems, offering an adjustment range of 380-500V. It supports both WYE and Delta system configurations.
What are the environmental operating limits for this 3-phase monitor?
The unit is designed to operate within a temperature range of -20° to +131° F. It tolerates 0-97% humidity without condensation.
What is the response time and output contact rating of the Model 2594?
The Model 2594 has a response time of 0.05 seconds. Its output contacts are DPDT 600VAC, rated at 3A at 480/600VAC 80% PF.