C200-480V

C200-480V

The Model 200 3-Phase Voltage Unbalance Monitor, SKU C200, offers essential protection for industrial three-phase systems. Voltage unbalance can lead to motor overheating and premature equipment failure. This monitor detects deviations from nominal 480VAC, ensuring system integrity. With a rapid 100ms response time and a precise ±0.1% repeat accuracy, it provides reliable fault detection. Users can adjust unbalance thresholds from 2% to 10% to suit specific application requirements. Its DPDT 10 amp contacts facilitate direct control of protective devices. The unit operates effectively across a -20° to +131° F temperature range, supporting continuous operation in diverse industrial environments. This device helps maintain system health and extends equipment lifespan.

The Model 200 3-Phase Voltage Unbalance Monitor is designed to
continuously monitor a three-phase line for unbalanced voltage
conditions. This device will only energize the relay if an unbalance
exists. Zero volts on all three phases is considered a balanced
condition. This allows the Model 200 to be used with shunt breakers, so
that the breaker can shut off the main power without tripping the
monitor. The solid-state sensing circuit drives an internal
electromechanical relay. Indicator lights on the monitor show when the
voltage balance is within an acceptable range; when an unbalance exists;
and when the relay is actually tripped. When an acceptable voltage
balance is reapplied, the Model 200 will automatically reset the relay.

Out of stock

Specifications

Nominal AC Voltages480VAC
Voltage Range± 15%
Frequency60Hz
Power Consumption (per phase)2W
Transient Protection2500VRMS for 10ms
Repeat Accuracy± 0.1% (fixed conditions)
Unbalance Adjustment2% to 10%
Response Time100ms
Reset TimeFixed 1 sec
Dropout TimeAdjustable 0.2 to 20 seconds
Reset TypeAutomatic
Dead Band0.5% max
Contact RatingDPDT 10 amps at 240VAC resistive
Expected Relay Life (Mechanical)10 million operations
Expected Relay Life (Electrical)100,000 operations at rated load
Operating Temp-20° to +131° F
Humidity Tolerance0-97% w/o condensation
MountingSurface
Enclosure MaterialABS plastic
Mounting Hole Diameter0.19

FAQs

What is the operating voltage and frequency for the Model 200 monitor?
The Model 200 is designed for 480VAC nominal systems with a ±15% voltage range and operates at 60Hz.
What is the expected relay life and contact rating of this device?
The relay has an expected mechanical life of 10 million operations and an electrical life of 100,000 operations at rated load. It features DPDT 10 amp contacts at 240VAC resistive.
How quickly does the Model 200 respond to an unbalance condition and what is its adjustment range?
The monitor has a response time of 100ms. Its unbalance adjustment range is from 2% to 10%.