B265-240VAC

B265-240VAC

The Model 265 3-Phase Monitor provides essential protection for industrial equipment. It continuously monitors for phase loss, low voltage, and phase reversal, safeguarding critical systems from potential damage. Featuring an automatic reset type and an adjustable reset time from 20 to 300 seconds, it ensures operational continuity following fault conditions. The unit operates reliably across a nominal AC voltage of 208/240VAC, with an adjustment range of 160-240V, accommodating various power supply conditions. Its robust design, featuring a 50ms maximum response time and SPDT 10 amp output contacts, contributes to system stability and control. With a power consumption of 0.5W and an operating temperature range of -20° to +131° F, this monitor is engineered for consistent performance in demanding environments, offering dependable protection for three-phase applications.

The Model 265 3-Phase Monitor continuously monitors 3-phase Wye or Delta
systems for phase loss, low voltage and phase reversal. When properly
adjusted, the Model 265 Monitor will detect phase loss on a loaded motor
even when regenerated voltage is present. The solid-state sensing
circuit drives an internal relay, in a fail-safe configuration, i. e. ,
the relay is energized when correct voltage and phase rotation are
applied. Operating power for the Model 265 is drawn from the 3-phase
lines being monitored. An adjustable timer delays restarting of the
load, allowing up to five minutes for compressor head pressures to bleed
off, in the event of short-term power failures. The Model 265 Monitor
is not sensitive to line current, and can be used with any size motor or
compressor. Automatic and manual reset versions are available.

Out of stock

$346.00

Specifications

Reset TypeAutomatic
Monitored ParametersPhase loss, low voltage, phase reversal
Nominal AC Voltage (phase to phase)208/240VAC
Adjustment Range160-240V
Frequency60Hz
Power Consumption0.5W
Transient Protection2500 VRMS for 10ms
Repeat Accuracy± 0.1% of set point (fixed conditions)
Response Time50ms maximum
Reset TimeAdjustable - 20 to 300 seconds ±10%
Dead BandApproximately 2%
Output ContactsSPDT 10 amps at 240VAC resistive
Expected Relay Life - Mechanical10 million operations
Expected Relay Life - Electrical100,000 operations at rated load
Operating Temperature-20° to +131° F
Humidity Tolerance0-97% w/o condensation
Enclosure MaterialABS plastic
MountingSurface
Agency ApprovalsUL Recognized and CSA Certified

FAQs

What conditions does the Model 265 monitor for?
The Model 265 monitors for phase loss, low voltage, and phase reversal.
What is the operating voltage range for this monitor?
It operates at a nominal AC voltage of 208/240VAC, with an adjustment range of 160-240V.
What are the environmental specifications for the Model 265?
The operating temperature range is -20° to +131° F, with a humidity tolerance of 0-97% without condensation.