3-Phase Monitor

B2522BM-120V

The MODEL 2522 B2522BM 3-Phase Monitor offers essential protection for industrial systems. This device monitors for phase loss, low voltage, and phase reversal, ensuring operational integrity. Its DPDT contact configuration provides versatile control options, while the manual reset type allows for deliberate system re-engagement after fault conditions. With a nominal voltage of 120VAC and an adjustment range of 85-120VAC, it adapts to various power requirements. A rapid response time of 0.05 seconds minimizes potential equipment damage. The monitor operates efficiently with a power consumption of 0.75W and maintains performance across an operating temperature range of -20° to +131° F. Its robust ABS plastic enclosure and 2500 VRMS transient protection contribute to its reliability in demanding environments. This unit is compatible with both Wye and Delta systems, simplifying integration without requiring a neutral connection.

3Ph Pwr Mon Dpdt

DOWNLOADS:

b2522bm-120v

Specifications

Monitored ConditionsPhase Loss, Low Voltage, Phase Reversal
Reset TypeManual
Contact ConfigurationDPDT
Nominal Voltage120VAC
Max Input Voltage132VAC
Adjustment Range85-120VAC
Frequency60Hz
Power Consumption.75W
Transient Protection2500 VRMS for 10ms
Repeat Accuracy±0.1% of set-point (fixed conditions)
Response Time0.05 seconds
Reset Time0.05 seconds
Dead Band2%
Contact Rating5 amps, 115VAC resistive
Contact Rating870 VA, 30VDC, 300VAC
Expected Relay Life (Mechanical)10 million operations
Expected Relay Life (Electrical)100,000 operations at rated load
Operating Temperature-20° to +131° F
Humidity Tolerance97% w/o condensation
Enclosure MaterialABS plastic
Mounting11-pin socket (order separately)
Socket Part Number51X016
System CompatibilityWye or Delta systems
Neutral ConnectionNot required

FAQs

What conditions does the B2522BM 3-Phase Monitor detect?
It detects phase loss, low voltage, and phase reversal conditions.
What is the operating voltage specification for the B2522BM?
The nominal voltage is 120VAC, with an adjustment range from 85-120VAC.
What is the contact configuration and reset type of this monitor?
It features a DPDT contact configuration and a manual reset type.