Over & Under 3-Phase Monitor

A269R

The Model 269R Over & Under 3-Phase Monitor provides essential protection for industrial systems. It continuously monitors for critical conditions including high voltage, low voltage, phase loss, and phase reversal, safeguarding equipment from operational disruptions. With a robust design, it offers a repeat accuracy of ± 0.1% of set point and a mechanical relay life of 10 million operations, ensuring consistent performance over time. The adjustable reset time, ranging from 0.3 to 5 minutes, allows for application-specific configuration, enhancing operational flexibility. Operating within a temperature range of -20° to +130° F and tolerating 0-97% humidity without condensation, it is suitable for diverse industrial settings. Its 5-year unconditional warranty underscores its reliability in demanding environments, providing long-term assurance. This monitor is a practical solution for maintaining system integrity and minimizing downtime in critical three-phase applications.

Volt Mon W/Restart Delay

DOWNLOADS:

a269r

Specifications

Monitored ConditionsHigh Voltage, Low Voltage, Phase Loss & Phase Reversal
Nominal AC Voltage (phase to phase)120VAC
Adjustable Range - Upper110-145V
Adjustable Range - Lower80-115V
Frequency60Hz
Power Consumption1.5W
Transient Protection2500VRMS for 10ms
Repeat Accuracy± 0.1% of set point (fixed conditions)
Response Time4 ±2 seconds fixed
Reset TimeAdjustable 0.3 to 5 minutes
Reset TypeAutomatic
Dead BandApproximately 2%
Output ContactsSPDT 10A at 240VAC resistive
Expected Relay Life (Mechanical)10 million operations
Expected Relay Life (Electrical)100,000 operations at rated load
Operating Temperature-20° to +130° F
Humidity Tolerance0-97% w/o condensation
Enclosure MaterialABS Plastic
MountingSurface
Warranty5 Year Unconditional Warranty

FAQs

What voltage conditions does the A269R monitor detect?
The A269R monitors for high voltage, low voltage, phase loss, and phase reversal in 3-phase systems.
What is the operating temperature range for the Model 269R?
The Model 269R operates reliably within a temperature range of -20° to +130° F.
Can the reset time be adjusted on this 3-phase monitor?
Yes, the reset time is adjustable from 0.3 to 5 minutes, with an automatic reset type.