A258BM-480V-400HZ

A258BM-480V-400HZ

The Model A258BM 3-Phase Monitor provides essential protection for industrial systems. Operating at a nominal 480VAC with an adjustment range of 380-480VAC, this device safeguards equipment by detecting phase loss, low voltage, and phase reversal. Its MANUAL reset type ensures deliberate system restarts following an event. With a low power consumption of 3.7W and a rapid response time of 50ms drop out, it offers efficient and timely fault detection. The unit's output contacts are SPDT 10 amps at 240VAC resistive, supporting reliable control circuit integration. An expected mechanical relay life of 10 million operations and an electrical life of 100,000 operations at rated load underscore its long-term durability. This monitor is designed for consistent performance across an operating temperature range of -20° to +131° F, ensuring operational integrity in varied industrial settings.

The Model 258 continuously monitors 3-phase power lines for abnormal
conditions. When properly adjusted, the Model 258 monitor will detect
phase loss on a loaded motor even when regenerated voltage is present.
This device consists of a solid-state voltage and phase-angle sensing
circuit, driving an electromechanical relay. When correct voltage and
phase rotation are applied, the internal relay will energize. A fault
condition will de-energize the relay. When the fault is corrected, the
monitor will automatically reset (a manual reset version is also
available). The Model 258 does not require a neutral connection and
can be used with Wye or Delta systems. Voltage ranges are sufficiently
wide to allow for proper adjustment to existing conditions. Both TRIP
and NORM condition indicators are provided to aid in adjustment and
system trouble-shooting.

Out of stock

$194.00

Specifications

Reset TypeMANUAL Reset
Nominal AC voltage (phase to phase)480VAC
Case ColorRed
Adjustment range380-480VAC
Frequency60Hz
Power consumption3.7W
Protection FeatureDetects phase loss, low voltage, phase reversal
WarrantyFive year unconditional warranty
Transient protection2500VAC for 10ms
Repeat accuracy± 0.1% of set point (fixed conditions)
Response time50ms drop out
Dead bandApprox. 2%
Output contactsSPDT 10 amps at 240VAC resistive
Expected relay life (Mechanical)10 million operations
Expected relay life (Electrical)100,000 operations at rated load
Operating temperature-20° to +131° F
Humidity tolerance0-97% w/o condensation
Enclosure materialABS plastic cover
Mounting8-pin socket (**sold separately)
Agency approvalsUL Recognized* and CSA Certified

FAQs

What voltage range does the Model A258BM 3-Phase Monitor support?
The Model A258BM monitors nominal 480VAC systems, with an adjustable range from 380VAC to 480VAC.
What types of electrical faults does the A258BM detect?
This monitor detects phase loss, low voltage conditions, and phase reversal to protect connected equipment.
What is the expected operational lifespan of the relay contacts in the A258BM?
The relay contacts have an expected mechanical life of 10 million operations and an electrical life of 100,000 operations at rated load.
Select your currency