3-Phase Monitor

A246-400HZ

The Model 246 3-Phase Monitor provides essential protection for industrial systems. This device continuously monitors for phase loss, phase reversal, low voltage, and over voltage conditions, ensuring operational integrity. Its automatic reset functionality minimizes downtime by restoring system operation without manual intervention once faults are cleared. With a nominal AC voltage of 120V and adjustable ranges for both low (85-125V) and high (110-140V) thresholds, it adapts to specific application requirements. The monitor features robust transient protection up to 2500V for 10ms, safeguarding against power disturbances. A repeat accuracy of ±0.1% of set point ensures consistent performance. Designed for reliability, it offers a mechanical relay life of 10 million operations and operates effectively across a wide temperature range from -20° to +131° F. This unit contributes to maintaining stable and protected three-phase electrical systems, enhancing equipment longevity and operational safety.

Ph Pwr Mon

DOWNLOADS:

a246-400hz

Specifications

Monitors forPhase Loss or Reversal, Low and Over Voltage
Reset TypeAutomatic
Agency ApprovalCSA
Warranty5 Year Unconditional Warranty
Nominal AC Voltage120
Adjustment Range (Low)85-125 V
Adjustment Range (High)110-140 V
Frequency60Hz
Power Consumption (per phase)1W
Transient Protection2500V for 10ms
Repeat Accuracy±0.1% of set point (fixed conditions)
Response/Reset Time50ms
Dead Band2%
Contact RatingSPDT 10A at 240VAC resistive
Expected Relay Life (Mechanical)10 million operations
Expected Relay Life (Electrical)100,000 at rated load
Operating Temperature-20° to +131° F
Humidity Tolerance0-97% w/o condensation
Enclosure MaterialABS plastic
Mounting8-pin socket *order separately
Max Input Voltage140VAC

FAQs

What conditions does the A246 3-Phase Monitor detect?
The A246 monitor detects phase loss, phase reversal, low voltage, and over voltage conditions in a 3-phase system.
What are the adjustable voltage ranges for the A246 monitor?
The low voltage adjustment range is 85-125V, and the high voltage adjustment range is 110-140V for the A246.
What is the operational temperature range for the A246 3-Phase Monitor?
The A246 3-Phase Monitor is designed to operate effectively within a temperature range of -20° to +131° F.