The Model 200 3-Phase Voltage Unbalance Monitor provides essential protection for industrial systems. This device continuously monitors three-phase AC lines, detecting voltage imbalances that can lead to equipment damage or operational inefficiencies. Its adjustable unbalance threshold, ranging from 2% to 10%, allows for precise application tailoring. A rapid 100ms response time ensures prompt detection of anomalies, minimizing potential downtime. The integrated DPDT 10 amp contacts facilitate direct control of protective circuits, rated for 100,000 electrical operations at load. With a robust design, including transient protection up to 2500VRMS for 10ms and an operating temperature range of -20° to +131° F, the Model 200 maintains system integrity in demanding environments. Its automatic reset function further streamlines operational continuity, reducing manual intervention. The unit's compact dimensions and surface mounting simplify installation within existing control panels.

The Model 200 3-Phase Voltage Unbalance Monitor is designed to
continuously monitor a three-phase line for unbalanced voltage
conditions. This device will only energize the relay if an unbalance
exists. Zero volts on all three phases is considered a balanced
condition. This allows the Model 200 to be used with shunt breakers, so
that the breaker can shut off the main power without tripping the
monitor. The solid-state sensing circuit drives an internal
electromechanical relay. Indicator lights on the monitor show when the
voltage balance is within an acceptable range; when an unbalance exists;
and when the relay is actually tripped. When an acceptable voltage
balance is reapplied, the Model 200 will automatically reset the relay.

Out of stock

Specifications

Nominal AC Voltages120VAC
Voltage Range± 15%
Frequency60Hz
Power Consumption (per phase)0.5W
Transient Protection2500VRMS for 10ms
Repeat Accuracy± 0.1% (fixed conditions)
Unbalance Adjustment2% to 10%
Response Time100ms
Reset TimeFixed 1 sec
Dropout TimeAdjustable 0.2 to 20 seconds
Reset TypeAutomatic
Dead Band0.5% max
Contact RatingDPDT 10 amps at 240VAC resistive
Expected Relay Life (Mechanical)10 million operations
Expected Relay Life (Electrical)100,000 operations at rated load
Operating Temp-20° to +131° F
Humidity Tolerance0-97% w/o condensation
MountingSurface
Enclosure MaterialABS plastic
Mounting Hole Diameter0.19

FAQs

What are the primary voltage specifications for the Model 200 monitor?
The Model 200 operates with a nominal AC voltage of 120VAC, accommodating a voltage range of ±15%. It is designed for 60Hz frequency applications.
How quickly does the Model 200 respond to voltage unbalance conditions and what is its adjustment range?
The Model 200 has a response time of 100ms. Its unbalance adjustment range is from 2% to 10%, allowing for application-specific sensitivity settings.
What are the contact rating and environmental tolerances of the Model 200?
The Model 200 features DPDT 10 amp contacts at 240VAC resistive. It operates within a temperature range of -20° to +131° F and tolerates 0-97% humidity without condensation.