662

662

The 662 Pump Up Control provides reliable liquid level management for industrial applications. Its automatic reset function and two adjustable trip points ensure precise control over fluid levels. Operating on 24VDC with a 4-20mA input signal, this unit integrates seamlessly into existing control systems. The robust design accommodates operating temperatures from -13° to +122° F and humidity up to 97% without condensation, ensuring consistent performance in demanding environments. With a mechanical relay life of 10 million operations, the control offers extended operational longevity, reducing maintenance frequency. Its compact ABS plastic enclosure and 11-pin socket mounting facilitate straightforward installation and maintenance procedures. Integrated PUMP UP and INPUT LOOP ERROR LEDs provide immediate operational status feedback, enhancing system diagnostics and uptime for critical processes.

The Model 662 Pump Up Control, part of the 600 series line of
instrumentation controls, is designed to monitor andmaintain liquid
levels. A user-provided 4-20mA current loop represents the liquid level,
and output connections are provided for pump control. The HIGH
ADJUSTsetpoint, and the LOW ADJUST setpoint, are field adjustable. If
the input falls below the low setpoint, the PUMP UP relay energizes, and
remains that way until the input rises above the high setpoint. The high
setpoint must always be set above the low setpoint. Top-mounted LEDs on
the Model 662 show system status. The PUMP UP LED turns ON when the
input falls to 10% below the low setpoint, and resets when the input
rises above this level. An INPUT LOOP ERROR LED turns ON if the input is
outside the 4-20mA range. A Time Mark Model 650 Loop Power Supply (or
equivalent) is required to provide the 24 VDC operating voltage. A Time
Mark Model 672-15 Pressure Transducer (or equivalent) is required to
provide the input signal.

Out of stock

Specifications

Reset TypeAutomatic reset
Trip PointsTwo adjustable trip points
Warranty5-YEAR UNCONDITIONAL WARRANTY
Operating Voltage24VDC ±5%
Supply Current30mA maximum
Input Signal4-20mA
Input Resistance50Ω
Input Loop Error (High)23-25mA
Input Loop Error (Low)2-3mA
Adjustments4-20mA
Low Alarm Trip Point10% below low trip point
Contact RatingResistive: 10 amps at 240VAC
Operating Temperature-13° to +122° F
Expected Relay Life (Mechanical)10 million operations
Expected Relay Life (Electrical)100,000 at rated load
Humidity Tolerance0-97% w/o condensation
Enclosure MaterialABS plastic
Mounting11-pin socket (*order separately)
Required Socket P/N51X016
IndicatorsPUMP UP LED, INPUT LOOP ERROR LED
Dimension Tolerance±0.06

FAQs

What are the power and input signal specifications for the 662 Pump Up Control?
The unit operates on 24VDC ±5% with a maximum supply current of 30mA. It accepts a 4-20mA input signal with an input resistance of 50Ω.
What are the environmental operating limits for the 662 Pump Up Control?
It is designed for an operating temperature range of -13° to +122° F. The humidity tolerance is 0-97% without condensation.
How does the 662 Pump Up Control manage its operational status and relay function?
The control features an automatic reset type and two adjustable trip points. It includes PUMP UP and INPUT LOOP ERROR LEDs for status indication. The mechanical relay life is 10 million operations.