The MODEL 442 Multi-Stage Alternator, SKU 442-240, provides reliable control for multi-motor/pump systems. Its selectable modes support single, duplex, triplex, and quadraplex configurations, ensuring operational flexibility across diverse applications. The unit features power loss memory, retaining the operational sequence during power interruptions to maintain system integrity and minimize downtime. With an expected relay life of 50 million mechanical operations and 100,000 electrical operations at rated load, it offers sustained performance and durability. Operating within a -20° to +140° F temperature range and tolerating 0-97% humidity without condensation, this alternator is designed for demanding industrial environments. Its 240VAC input and 5A output contact rating facilitate straightforward integration into various control panels, providing a robust solution for sequencing operations.

4Stage Alt W/Stop

DOWNLOADS:

442-240v

Specifications

Input Voltage240VAC +/- 10% 50/60Hz
Power Consumption6.0 watts
Transient Protection2500 VRMS for 10ms
Delay Between Relay Operations5 seconds
Output Contact RatingSPST 5A at 240VAC or 5A at 30VDC resistive
Input Contact Requirement0.001 amp at 12VDC
Expected Relay Life, Mechanical50 million operations
Expected Relay Life, Electrical100,000 ops at rated load
Operating Temperature-20° to +140° F
Humidity Tolerance0-97% w/o condensation
Enclosure MaterialABS plastic
Selectable ModesSingle Motor/Pump, Two Motor/Pump (duplex), Three Motor/Pump (triplex), Four Motor/Pump (quadraplex)
Power Loss MemoryUnit remembers which motor/pump is next during power loss
Operation ModeSequence-On, Simultaneous-Off
WarrantyOne year from date of manufacture

FAQs

What input voltage is required for the 442-240 Multi-Stage Alternator?
The 442-240 Multi-Stage Alternator requires an input voltage of 240VAC +/- 10% at 50/60Hz.
What is the output contact rating for the 442-240 Multi-Stage Alternator?
The output contact rating is SPST 5A at 240VAC or 5A at 30VDC resistive.
What motor/pump configurations can the 442-240 Multi-Stage Alternator manage?
It supports selectable modes for single, two (duplex), three (triplex), and four (quadraplex) motor/pump operations.