4062-15PSI
The MODEL 4062 Pump-Up Controller offers precise liquid level management for industrial applications. Its 4-20mA input with scalable output ensures accurate signal interpretation and control. Integrated seal fail monitoring provides early detection of pump issues, minimizing downtime and maintenance costs. Duplex pump alternation extends pump life by distributing operational wear evenly. Operators benefit from Hand-Off-Auto controls for flexible system management and dual run-time meters for comprehensive performance tracking. RS-485/Modbus communications facilitate seamless integration into existing control networks, enabling remote monitoring and data acquisition. The unit's UL Recognized status confirms adherence to safety and performance standards. This controller is designed for reliable operation within an operating temperature range of +14° to +122° F, ensuring consistent performance in diverse environments. Its robust 16 gauge steel enclosure provides durability.
The Model 4062 Pump-Up Controller provides total control for duplex
pumping systems. The Model 4062 monitors, controls and displays the
liquid level in a tank or reservoir, up to a depth of 34.6 feet. The
input to the Model 4062 can be from any 2 or 3-wire transducer with a
4-20mA output that represents 0 to 34.6 feet. A 24VDC regulated probe
supply is included. A Level Simulator is provided to aid in programming
these five set points; Low Alarm, Level 2, Level 1, Pumps Off and High
Alarm. A universal zero to 30 second On Delay can be programmed to
prevent outputs from closing due to input fluctuations caused by
turbulent conditions. An additional 4-20mA output with zero and span
controls is provided for a chart recorder or other external device. Four
heavy-duty 10 amp, 120V contacts are provided for pump control and alarm
activation. An auto-dialer or other emergency device can be activated
with the SPDT power loss relay. This relay is held open when power is
applied. Communications capable via RS-485/Modbus. Pump outputs include
duplex alternation as well as hand-off-auto switches. Pump run-time can
be displayed for each pump with tenth of an hour resolution, up to
99,999. 9 hours. The Model 4062 can be panel-mounted (11 1/8 x 4 5/8),
same as Time Mark Models 403, 404, 4042 and 4052, or surface-mounted
using the optional surface-mounting kit, Model 4000.
Out of stock
$1,942.00
Specifications
| Input Voltage | 120VAC ± 10% 50/60Hz |
|---|---|
| Power Consumption | 8W |
| Signal Input | 4-20mA (optional 0-5V), 2 or 3 wire |
| Signal Input Load | 250 ohms |
| Dead Band | 1% of full scale |
| Repeat Accuracy | ± 1% of scaled (fixed conditions) |
| Display Type | 6 digit red LED display |
| Display Range, Level | 00.0 to 346 ft |
| Display Range, Runtime | zero to 99,999.9 hours |
| Display Range, Delay | zero to 30 seconds |
| Display Resolution | 1 decimal place |
| Control Contacts | 4 SPDT 10A at 120VAC resistive |
| Power Loss Relay | 1 SPDT 5A at 120VAC resistive |
| Signal Output Load | 300 ohms |
| Probe Supply | 24VDC regulated |
| Setpoints | 3 levels, 2 alarms, all user-adjustable |
| Operating Temperature | +14° to +122° F |
| Humidity Tolerance | 0-97% w/o condensation |
| Enclosure Material | 16 gauge steel |
| Termination | removable terminal strips |
| Agency Approvals | UL Recognized (U.S. & Canadian) |
| Feature | 4-20mA Input/Scalable Output |
| Feature | Seal Fail Monitoring |
| Feature | Duplex Pump Alternation |
| Feature | Hand-Off-Auto Controls |
| Feature | Dual Run-time Meters |
| Feature | RS-485/Modbus Communications |
| Panel Mount Cutout | 11.13" x 4.63" |
| Warranty | one year from the date of manufacture |