404-115VAC

404-115VAC

The MODEL 404 Liquid Level Sensor provides precise liquid depth monitoring for industrial applications. Its robust design ensures reliable operation across a -20° to +122° F temperature range, accommodating diverse environmental conditions. With a maximum liquid level display of 34.6 feet and a calibration accuracy of ± 2%, this sensor delivers consistent and dependable data for critical processes. The integrated 4-20mA output facilitates seamless integration into existing control systems, providing proportional signal outputs. Four adjustable trip points offer flexible control options for various operational requirements. Solid-state outputs enhance system longevity and reduce maintenance needs. Moisture-protected circuits contribute to its durability in challenging environments, preventing performance degradation. This unit is engineered for dependable performance, minimizing operational interruptions and supporting efficient process management through accurate level detection...-

The Model 404 Liquid Level Sensor operates in conjunction with a Model
403 Controller for bubbler-type duplex pumping systems. The 404 contains
an air pressure-to-voltage transducer and requires only a small air
compressor capable of 15 psi to operate the system down to approximately
35 feet. The Model 404s four outputs are designed to replace the float
switch inputs to a Model 403, or to be used with a Model 448 output
Relay Board. A 4-20mA signal output provides for other control
applications. A 3-digit LED display continuously shows the liquid level
to a tenth of a foot when the Display Control switch is in the Liquid
Level position. Other settings of the switch allow setting of the liquid
level trip points. LED indicators illuminate as the levels are exceeded.
A test control allows the trip settings to be checked without actually
raising or lower the liquid level.

Out of stock

$1,910.00

Specifications

Input voltage105-130VAC
Input frequency47-65Hz
Power consumption2W
Air pressure input0-15 psi
Input air supply fittingRequires 3/16" I.D. tubing
Maximum liquid level displayed34.6 feet
Calibration accuracy± 2%
Repeat accuracy (fixed condition)± 1%
Repeat accuracy (0-60° C)± 2%
Dead band0.1 foot
Switching outputs4 open-collector transistors rated for regulated 12VDC, 10mA, maximum. Designed as inputs for the Model 403 Liquid Level Controller or Model 448 Output Relay Board
Signal outputs4-20mA output proportional to 0-34.6 feet of water
Operating temperature-20° to +122° F
Storage temperature-4° to +158° F
Humidity tolerance0-97% without condensation
Case material20 gauge Steel
TerminationRemovable terminal strip
FeatureDigital display of water depth
FeatureSolid-state outputs
FeatureFour adjustable trip points
Feature4-20mA output
FeatureMoisture protected circuits
WarrantyThis product is warranted to be free from defects in materials and workmanship for one year.

FAQs

What are the power requirements for the MODEL 404 Liquid Level Sensor?
The sensor requires an input voltage of 105-130VAC at 47-65Hz, with a power consumption of 2W.
What is the maximum liquid level the MODEL 404 can display and its accuracy?
It can display a maximum liquid level of 34.6 feet with a calibration accuracy of ± 2% and a dead band of 0.1 foot.
How does the MODEL 404 provide output signals and switching capabilities?
It provides a 4-20mA output proportional to 0-34.6 feet of water and includes four open-collector transistor switching outputs.