365-L-1HR
The Model 365 Retriggerable One-Shot Timer provides precise control for industrial applications. Its high-accuracy digital input allows for flexible timing ranges, from 0.1 seconds up to 1023 minutes. With a repeatability of ±0.1% and an accuracy of ±2%, this device ensures consistent and reliable operation across various cycles. The DPDT contact configuration and a robust 240VAC @ 10A resistive contact rating support diverse load requirements in demanding environments. Designed for long-term reliability, it features transient protection up to 775V, 80 Joules, safeguarding against electrical disturbances. The timer operates effectively across a wide temperature range, from -20°F to 140°F. Its NORYL plastic enclosure and UL Recognized/CSA Certified status underscore its robust construction and adherence to industry standards, providing a dependable solution. A 5-year unconditional warranty further supports its long-term utility.
The Model 335 and 365 Retriggerable One-Shot Timers are functionally
interchangeable. The Model 335 is a DPDT potentiometer (knob-adjust)
timer while the Model 365 is a DPDT, high-accuracy digital input timer.
Solidstate timing circuits in each model drive an internal
electromechanical relay. With power applied to the coil, when the
initiate switch (dry contact) is closed, the relay will energize for the
time period set by the user. At the end of the preset time period, the
relay will de-energize. If the initiate switch opens and then closes
multiple times while the relay is energized (i. e. it is retriggered),
the relay will then restart the delay time. The relay will remain
energized until the retriggering stops and the delay time ends. When
power is removed, the relay will de-energize. An SG version of this
model is available using silver with gold flash contacts. Models 335 and
365 are UL Recognized and CSA Certified.
Out of stock
Specifications
| Warranty | 5-Year Unconditional Warranty |
|---|---|
| Adjustment Type | High-accuracy digital input |
| Contact Configuration | DPDT |
| Config: Voltage | L = 10-28V AC/DC; H = 40-260V AC/DC |
| Config: Timing Range | .1SEC: 0.1 - 102.3 Sec.; 1SEC: 1 - 1023 Sec.; 1MIN: 1 - 1023 Min. |
| Accuracy | ± 2% |
| Repeatability | ± 0.1% |
| Recycle Time | 100ms |
| Operating Temperature | -20°F to 140°F |
| Contact Rating | DPDT, 240VAC @ 10A resistive |
| Transient Protection | 775V, 80 Joules |
| Humidity Tolerance | 0-97% w/o condensation |
| Enclosure Material | NORYL Plastic |
| Mounting | 11-pin socket (not included) |
| Agency Approval | UL Recognized and CSA Certified |
| Config: Options | /C = Custom (Voltage and/or Timing); /SG = Silver with Gold Flash Contacts |
| UL Spec: Input Voltage | 10-28V AC/DC OR 40-260V AC/DC |
| UL Spec: Power | 3 Watts Max |
| UL Spec: Output (Resistive) | 240V AC, 10A |
| UL Spec: Output (General Use) | 120V AC, 4A; 240V AC, 2A |
| UL Spec: Output (Pilot Duty) | C300 |
| UL Spec: Pilot Duty (120V) | Make 15A, Break 1.5A |
| UL Spec: Pilot Duty (240V) | Make 7.5A, Break 0.75A |
| LED Status: Energized | Green |
| LED Status: De-energized | Red |
| LED Status: Relay is Timing | Flashing (Green or Red) |