Override Timer

349-5

The MODEL 349 series Override Timer provides precise, incremental control for various industrial applications. Its operation allows for 15 steps of 5-minute increments, totaling up to 75 minutes of timed output. Users can extend the timing duration with each button press, ensuring flexibility in operational sequences. A binary numbered indicator system clearly displays the remaining time, enhancing operational awareness. This unit integrates seamlessly into standard wall switch boxes, simplifying installation. With a contact rating of SPDT 10A at 240VAC resistive and transient protection up to 2500V for 10ms, it offers reliable performance in demanding environments. The timer's design prioritizes functional utility and consistent output, making it suitable for systems requiring specific, adjustable timing protocols. Its robust ABS plastic enclosure ensures durability, while a low power consumption of 2W maximum contributes to operational efficiency. The wide operating temperature range from -13°F to +140°F further supports its application in diverse industrial settings.

Override Timer

DOWNLOADS:

349-5

Specifications

Supply Voltage24VAC ± 20% or 120VAC ± 10%
Timing Range15 steps of 5 min.
Timing Accuracy± 2% per step
Recycle Time100ms
Input Frequency50-400Hz
Operating Temp-13°F to +140°F
Power Consumption2W
Transient Protection2500V for 10ms
Contact RatingSPDT 10A at 240VAC resistive
Enclosure MaterialABS plastic
MountingUses Standard Wall Switch Box
Time Delay15 steps: 5 MIN Increments
Maximum Delay75 minutes
OperationAfter the start button is pressed, the internal relay pulls in for one timing increment. Each additional press of the button adds one timing increment to the time, up to 15 increments total. The 16th press of the button drops out the relay.
IndicatorBinary numbered indicator lights show remaining time.
WarrantyOne year

FAQs

How is the timing duration adjusted on the 349-5 Override Timer?
The timing duration is adjusted in 5-minute increments, up to a maximum of 75 minutes (15 steps). Each button press adds one increment to the active timing cycle.
What are the power requirements for the 349-5 Override Timer?
The unit accepts a supply voltage of 24VAC ± 20% or 120VAC ± 10%, with an input frequency range of 50-400Hz.
How does the 349-5 Override Timer indicate remaining time?
The timer features binary numbered indicator lights that clearly display the remaining time during operation.