Instant & Operate Delay Timer

333-L-180SEC

The Model 333 Instant & Operate Delay Timer provides essential functionality for industrial applications. Its broad voltage compatibility, spanning 10-28V AC/DC and 40-260V AC/DC, ensures integration across diverse systems. Users benefit from selectable timing ranges up to 300 seconds, offering precise control for various operational sequences. The unit's dual SPDT relays are rated for 10A at 240VAC resistive loads, supporting robust switching requirements. With a wide operating temperature range from -20°F to +140°F and UL Recognized and CSA Certified approvals, this timer delivers consistent performance. Its ± 5% accuracy and ± 2% repeatability ensure dependable operation. The NORYL plastic enclosure provides durability. A 5-year warranty underscores its reliability in demanding environments, minimizing downtime and maintenance concerns. This timer is designed for sustained utility in critical timing circuits.

Instnt&Op Dly Tmr

DOWNLOADS:

333-l-180sec

Specifications

Adjustment Typeknob adj.
VoltageL = 10-28V AC/DC; H = 40-260V AC/DC
Timing range10SEC: 1 - 10 Sec.; 60SEC: 1 - 60 Sec.; 180SEC: 1 - 180 Sec.; 300SEC: 1 - 300 Sec.
Accuracy± 5%
Repeatability± 2%
Operating temp-20°F to +140°F
Recycle time100ms
ContactsTwo SPDT Relays
Contact rating10A at 240VAC resistive
Transient protection775V, 80 Joules
Humidity tolerance0-97% w/o condensation
Enclosure materialNORYL Plastic
Mounting8-pin socket (not included)
Agency approvalUL Recognized and CSA Certified
Config: VoltageL (10-28V AC/DC), H (40-260V AC/DC)
Config: Timing Range10SEC, 60SEC, 180SEC, 300SEC
Config: Additional Options/C = Custom (Voltage and/or Timing), /SG = Silver with Gold Flash Contacts
Input Power3 Watts Max
Output (Resistive)240V AC, 10A
Output (General Use, 120V AC)4A
Output (General Use, 240V AC)2A
Output (Pilot Duty)C300
Pilot Duty (120V)Make 15A, Break 1.5A
Pilot Duty (240V)Make 7.5A, Break 0.75A
Warranty5-Year unconditional warranty
LED Indicator (Green)Energized
LED Indicator (Red)De-energized
LED Indicator (Flashing)Relay is Timing

FAQs

What voltage ranges does the Model 333 Instant & Operate Delay Timer support?
The Model 333 supports low voltage (L) from 10-28V AC/DC and high voltage (H) from 40-260V AC/DC.
What are the available timing ranges for this delay timer?
Timing ranges include 1-10 seconds, 1-60 seconds, 1-180 seconds, and 1-300 seconds, selectable via knob adjustment.
What are the contact specifications for the Model 333?
It features two SPDT relays with a contact rating of 10A at 240VAC resistive.