Frequency Monitor
The Model 29 Frequency Monitor provides essential oversight for industrial electrical systems. It precisely monitors frequencies within a 40Hz to 70Hz range, with an extended 320Hz to 560Hz option via jumper. Operating across an 80-550 VAC input, this unit ensures consistent performance. Dual SPDT output contacts, rated at 10 Amps for 240VAC, offer robust control capabilities. Configurable high and low frequency set points, along with adjustable trip delays and hysteresis, allow for tailored system protection. Its Lexan Polycarbonate enclosure and -20°F to +130°F operating temperature range ensure durability in demanding environments. Repeat accuracy is maintained at ± 0.5%. Automatic or manual restart options further enhance operational continuity, minimizing downtime. This monitor is a reliable component for maintaining system stability.
1Ph Freq Monitor
Specifications
| Input Voltage (VAC) | 80-550 Volts |
|---|---|
| Input Amps | 1mA |
| Input Frequency | 50/60Hz nominal |
| DC Power | 24 Volts, 2 watts |
| Output Rating (Resistive) | 240V AC, 10A |
| Output Rating (General Use, 120V) | 120V AC, 4A |
| Output Rating (General Use, 240V) | 240V AC, 2A |
| Output Rating (Pilot Duty) | C300 |
| Start-up Delay | 5 secs. Min. or Automatic reset delay setting (to allow for solid lock) |
| Frequency Range | 40Hz to 70Hz |
| Frequency Range (with jumper) | 320Hz to 560Hz with 400Hz jumper |
| Output Contacts | SPDT x 2 10 Amps @ 240VAC |
| Repeat Accuracy | ± 0.5% (fixed conditions) |
| Reset Type | Manual or Automatic |
| Expected Relay Life (Mechanical) | 10 million operations |
| Expected Relay Life (Electrical) | 100,000 min. at rated load |
| Operating Temperature | -20°F to +130°F |
| Humidity Tolerance | 0-97% w/o condensation |
| Enclosure Material | Lexan Polycarbonate |
| Mounting | Din Rail 35mm |
| Accuracy | +/- 0.5% |
| Setup Option: Frequency range select | 50/60Hz (Default), 400Hz |
| Setup Option: High frequency | Enable/Disable (Factory Enabled, Set point = 70Hz, Delay =5S) |
| Setup Option: High frequency Set point Range | Low Set +1% to 600Hz in 0.5Hz steps |
| Setup Option: High trip delay | 0 to 20.0 seconds in 0.1Sec steps |
| Setup Option: Low frequency | Enable/Disable (Factory Enabled, Set point = 40Hz, Delay = 5S) |
| Setup Option: Low frequency Set Range | 40 to High Set -1% in 0.5Hz steps |
| Setup Option: Low trip delay | 0 to 20.0 seconds in 0.1Sec steps |
| Setup Option: Relay operation | Frequency High/Low option, Separate High/Low relays, DPDT, Other faults DPDT (Factory = HI-LO) |
| Setup Option: Relay operation on fault | De-energize on fault, Energize on fault (Factory De-energize on fault) |
| Setup Option: High/Low Hysteresis range | 1 to 15% in 1% increments (Factory Enabled, Factory = 5%) |
| Setup Option: Restart | Automatic or Manual (Factory Automatic) |
| Setup Option: Automatic Restart Delay range | 0 to 300.0 Seconds in 0.1Sec steps (Factory = 5S) |
| Setup Option: Restore factory settings | No (Default), YES |
| Warranty | one year |