279B-120V

279B-120V

The Model 279B-120 DC Current Monitor provides reliable current monitoring for industrial applications. Operating on 120VAC, it handles a 1-10 Amps current range with a maximum continuous current of 15 Amps. Its robust design includes transient protection up to 2500 VRMS for 10ms, safeguarding critical systems from electrical disturbances. Users can fine-tune performance with 0% to 100% hysteresis adjustment and select automatic or manual reset functionality for operational flexibility. The unit maintains a repeat accuracy of 1% maximum across an operating temperature range of -20° to +131° F, ensuring consistent performance in varied environments. With an expected mechanical relay life of 10 million operations and a 5-year unconditional warranty, the 279B-120 offers sustained operational integrity and reduced maintenance concerns. Its SPDT 10A output contacts provide versatile control for diverse system integrations.

The Model 279 DC Current Monitor is a single set-point DC current
monitor. It can sense either 1-10 Amps DC (24VAC or 120VAC) or 0.1-1
Amps DC (120VAC). The units have an input frequency of 50/60 Hz. The
standard version, the 279B, has a screwdriver adjustable trip and
hysteresis setting on top of the device. The hysteresis setting adjusts
from 0% to 100%, and can be set fully clockwise for manual reset
operation. A remote adjust version, the 279C, has a remote trip
adjustment and a remote reset button. An LED indicator is provided on
both versions to indicate when the relay is energized (current above the
trip setting. ) The 279B plugs into a standard 8-pin octal socket; the
279C plugs into a standard 11-pin socket.

Specifications

Current range1-10 Amps
Supply voltage120VAC
Power consumption5.3W
Input frequency50-60Hz
Maximum current15 Amps continuous
Maximum surge current100A for 100ms
Transient protection2500 VRMS for 10ms
Hysteresis adjustment0% to 100%
ResetAutomatic or Manual
Repeat accuracy1% maximum
Output contactsSPDT 10A at 240VAC resistive
Expected relay life (Mechanical)10 million operations
Expected relay life (Electrical)100,000 operations at rated load
Operating temperature-20° to +131° F
Humidity tolerance0-97% w/o condensation
Mountingsocket sold separately
Case materialABS plastic
Socket Type8-pin
Recommended Socket51X120
Adjustment TypeScrewdriver adjustable trip and hysteresis setting
IndicatorLED
Warranty5-Year Unconditional Warranty
Dimension Tolerance± 0.06

FAQs

What is the operating current range for the 279B-120?
The Model 279B-120 DC Current Monitor is designed for a current range of 1-10 Amps, with a maximum continuous current capacity of 15 Amps.
What are the environmental operating limits for this current monitor?
The unit operates reliably within a temperature range of -20° to +131° F and tolerates 0-97% humidity without condensation.
Does the 279B-120 offer protection against power surges?
Yes, it includes transient protection rated at 2500 VRMS for 10ms and can withstand a maximum surge current of 100A for 100ms.
Select your currency
CAD Canadian dollar