2681-240VAC
The Model 2681 Voltage Band Monitor offers essential protection for industrial systems. This device precisely monitors both over and under voltage conditions, safeguarding equipment from potential damage due to power fluctuations. Its automatic reset function ensures continuous operation without manual intervention after a voltage event, minimizing downtime. Available in both AC and DC versions, the 2681 accommodates diverse application requirements, supporting nominal voltages from 24vac to 240vac and 12vdc to 230vdc. With a robust SPDT output and a 10A contact rating at 240vac resistive, it provides reliable control for connected loads. The unit's compact design and wide operating temperature range from -20° to +122°F make it suitable for various industrial environments, contributing to system longevity and operational stability. Its set-point stability of ± 0.5% ensures consistent performance.
The Model 2681 Voltage Band Monitor is a dual set-point voltage monitor.
Input voltages between the upper and lower set-points will cause the
output contacts to pull in (contacts 1 & 3 closed) and the LED
indicator to illuminate. Input voltages above or below the set-points
will cause the output contacts to drop out (contacts 1 & 4 closed)
and extinguish the LED indicator. The Model 2681 is available in AC or
DC versions. AC models of the 2681 are not frequency sensitive and can
be used on systems from 50 to 400 Hz. The voltage set-points are
screwdriver adjustable over a wide operating range. The SPDT output
configuration is identical to the configuration of general purpose
relays. This unit requires a standard 8-pin socket for mounting.
Out of stock
$288.00
Specifications
| Output Configuration | SPDT Output in Standard Relay Configuration |
|---|---|
| Function | Monitors Over and Under Voltage |
| Available Versions | AC or DC |
| Reset Type | Automatic Reset |
| Config: Nominal AC Voltage | 24vac, 120vac, 208vac, 240vac |
| Config: Max Input Voltage (AC) | 32vac, 160vac, 250vac, 285vac |
| Config: Under Voltage Range (AC) | 19-24vac, 90-120vac, 185-208vac, 200-240vac |
| Config: Over Voltage Range (AC) | 24-29vac, 120-150vac, 208-240vac, 240-270vac |
| Input Frequency (AC Models) | 50-400 Hz |
| Config: Nominal DC Voltage | 12vdc, 24vdc, 28vdc, 48vdc, 110vdc, 230vdc |
| Config: Max Input Voltage (DC) | 17vdc, 32vdc, 37vdc, 62vdc, 145vdc, 270vdc |
| Config: Under Voltage Range (DC) | 10-12vdc, 19-24vdc, 22-28vdc, 38-48vdc, 85-110vdc, 175-230vdc |
| Config: Over Voltage Range (DC) | 12-15vdc, 24-29vdc, 28-34vdc, 48-58vdc, 110-135vdc, 230-260vdc |
| Power Consumption | 2 watts max |
| Set-point Stability | ± 0.5% of set-point |
| Dead Band | 2% |
| Polarity Protection | DC versions only |
| Trip Response | 0.5 sec fixed (± 0.1 sec) |
| Reset Time | 0.1 sec |
| Output Contacts | SPDT |
| Contact Rating | 10A at 240vac resistive |
| Expected Relay Life, Mechanical | 10 million operations |
| Expected Relay Life, Electrical | 100,000 at rated load |
| Operating Temperature | -20° to +122°F |
| Humidity Tolerance | 97% w/o condensation |
| Mounting | 8-pin socket (*order separately) |
| Case Material | ABS plastic |
| Dimension Tolerance | ± 0.06 |