AC/DC Voltage Monitor

2629

The Model 2629 AC/DC Voltage Monitor provides essential protection for industrial systems. This device accurately monitors both AC and DC voltages from 15 to 260 Volts, ensuring operational integrity across diverse power sources. Its adjustable trip points allow for precise configuration to specific application requirements, preventing equipment damage from voltage fluctuations. Featuring an automatic reset and a DPDT relay with a 5A at 240VAC resistive contact rating, the unit offers reliable performance and control. With a robust operating temperature range of -13° to +122° F and 2500V transient protection, it maintains stability in demanding environments. The unit's compact design and 8-pin socket mounting simplify installation. A 5-year unconditional warranty underscores its durability and long-term value in critical voltage monitoring applications, minimizing downtime and maintenance concerns.

Volt Mon Ac/Dc

DOWNLOADS:

2629

Specifications

FunctionMonitors Over or Under Voltage
Monitored VoltageAC or DC from 15 to 260 Volts
Trip PointsAdjustable
Reset TypeAutomatic
Relay TypeDPDT Relay
Supply Voltage15 to 260 VAC or VDC
Max Supply Voltage280VAC or 300VDC
Power Consumption1.5 watts
Transient Protection2500V for 10ms
Setpoint Stability± 1%
Response Time1 sec ON / 100ms OFF
Dead Bandless than 5% all ranges
Contact RatingDPDT 5A at 240VAC resistive
Expected Relay Life (Mechanical)5 million operations
Expected Relay Life (Electrical)100,000 at rated load
Operating Temperature-13° to +122° F
Humidity Tolerance0-97% without condensation
Enclosure MaterialABS plastic
Mounting8-pin socket (*order separately)
Accessory Socket Part Number51X120
Dimension Tolerance± 0.06
IndicatorLED (Relay Energized)
Config: Voltage Type SelectionSwitch 4: ON=DC, OFF=AC
Config: Trip Level Range (Switches 123 = 000)15-50
Config: Trip Level Range (Switches 123 = 100)45-80
Config: Trip Level Range (Switches 123 = 010)75-110
Config: Trip Level Range (Switches 123 = 110)105-140
Config: Trip Level Range (Switches 123 = 001)135-170
Config: Trip Level Range (Switches 123 = 101)165-200
Config: Trip Level Range (Switches 123 = 011)195-230
Config: Trip Level Range (Switches 123 = 111)225-260
Warranty5-year Unconditional Warranty

FAQs

What voltage types and ranges can the Model 2629 monitor?
The Model 2629 monitors AC or DC voltage from 15 to 260 Volts. Its supply voltage range is also 15 to 260 VAC or VDC.
What are the relay specifications and expected operational lifespan of this monitor?
The unit features a DPDT relay with a contact rating of 5A at 240VAC resistive. Expected mechanical relay life is 5 million operations, and electrical life is 100,000 at rated load.
What environmental conditions can the Model 2629 withstand?
It operates within a temperature range of -13° to +122° F and tolerates 0-97% humidity without condensation. Transient protection is rated at 2500V for 10ms.