2628

2628

The Model 2628 AC/DC Voltage Monitor provides reliable voltage monitoring across a broad spectrum of industrial applications. It detects both over and under voltage conditions within a 15 to 260 Volt range, accommodating diverse system requirements. The automatic reset feature simplifies operation and minimizes manual intervention, enhancing system uptime. Its robust 10A at 240VAC resistive SPDT contact rating ensures dependable switching for connected loads, contributing to system integrity. Designed for demanding environments, the unit operates effectively from -13° to +122° F and offers 2500 V transient protection for 10ms. With a maximum power consumption of 1.5 watts, this monitor delivers consistent performance for critical voltage protection without significant energy draw. Its adjustable trip points allow for precise application tailoring.

The Model 2628 AC/DC Voltage Monitor is designed to continuously monitor
any AC or DC voltage from 15 to 260 volts. Input voltages below the
set-point cause the output contacts to de-energize. Input voltages above
the set-point cause the output contacts to energize. The dead band
between pull-in and drop-out is less than 5%. Dip switches are used on
the Model 2628 to choose between AC and DC voltage monitoring, and to
select one of the eight trip level ranges. Each trip level has a 35
voltage range, with a 5 volt overlap between the ranges. The unit has a
screwdriver adjustment to set the exact trip point within that 35 volt range.

Out of stock

$306.00

Specifications

FunctionMonitors Over or Under Voltage
Monitored Voltage Range15 to 260 Volts
Trip PointsAdjustable
Reset TypeAutomatic
Supply Voltage15 to 260 VAC or VDC
Max Supply Voltage280VAC or 300VDC
Power Consumption1.5 watts
Transient Protection2500 V for 10ms
Setpoint Stability± 1%
Response Time1 sec ON / 100ms OFF
Dead Bandless than 5% all ranges
Contact ConfigurationSPDT
Contact Rating10A at 240VAC resistive
Expected Relay Life (Mechanical)10 million operations
Expected Relay Life (Electrical)100,000 at rated load
Operating Temperature-13° to +122° F
Humidity Tolerance0-97% without condensation
Enclosure MaterialABS plastic
Mounting8-pin socket (*order separately)
Required Accessory8-pin socket number 51X120
Dimensions Tolerance± 0.06
Warranty5-year Unconditional Warranty
Config: Trip Level Range (Switches 123=000)15-50
Config: Trip Level Range (Switches 123=100)45-80
Config: Trip Level Range (Switches 123=010)75-110
Config: Trip Level Range (Switches 123=110)105-140
Config: Trip Level Range (Switches 123=001)135-170
Config: Trip Level Range (Switches 123=101)165-200
Config: Trip Level Range (Switches 123=011)195-230
Config: Trip Level Range (Switches 123=111)225-260
Config: Voltage Type Selection (Switch 4)ON=DC, OFF=AC

FAQs

What voltage ranges can the Model 2628 monitor?
The Model 2628 monitors voltages from 15 to 260 Volts. It accepts a supply voltage of 15 to 260 VAC or VDC.
What are the contact specifications for the relay output?
The relay features an SPDT contact configuration with a rating of 10A at 240VAC resistive. It has an expected electrical life of 100,000 operations at rated load.
What environmental conditions can the Model 2628 withstand?
The unit operates within a temperature range of -13° to +122° F and tolerates 0-97% humidity without condensation. It also provides 2500 V transient protection for 10ms.
Select your currency
CAD Canadian dollar