2621-48VDC

2621-48VDC

The Model 2621 Voltage Monitor offers precise voltage supervision for critical industrial applications. Its switch-selectable relay operation allows for flexible control logic, accommodating both 'on low' and 'off low' scenarios. With configurable nominal AC voltages including 24VAC, 120VAC, 208VAC, and 240VAC, and DC options like 12VDC, 24VDC, 48VDC, and 110VDC, this device adapts to diverse power systems. A robust 10A at 240VAC resistive contact rating ensures reliable switching for connected loads. The unit maintains set-point stability within ± 0.5% and operates effectively across a 14° to +122°F temperature range, tolerating 97% humidity without condensation. Its rapid 0.5-second trip response and 0.1-second reset time ensure timely system protection. The compact design and 8-pin socket mounting facilitate straightforward integration, providing consistent performance and protection for sensitive equipment.

The Model 2621 dual set point voltage monitor is designed to monitor
single phase equipment. The Normal LED indicates the relay is ENERGIZED.
Toggle switch settings are as follows: Off lo – Relay de-energizes at
Lo Trip – Relay energizes at Hi Trip On lo – Relay energizes at Lo
Trip – Relay de-energizes at Hi Trip The Model 2621 is available in AC
or DC versions. AC models of the 2621 are not frequency sensitive and
can be used on systems from 50 to 400 Hz. Dual set points are ideal for
battery charging applications.

Out of stock

$332.00

Specifications

Output ConfigurationSPDT
Relay OperationSwitch Selectable Relay On or Off on Low
Switch Position Logic (Off Lo)Lo Trip Set Point: Relay De-Energizes, Hi Trip Set Point: Relay Energizes
Switch Position Logic (On Lo)Lo Trip Set Point: Relay Energizes, Hi Trip Set Point: Relay De-Energizes
Config: Nominal AC voltages24VAC, 120VAC, 208VAC, 240VAC
Config: Max input voltage (AC)32VAC, 160VAC, 220VAC, 285VAC
Config: Under voltage range (AC)19-26VAC, 90-132VAC, 185-229VAC, 178-233VAC, 200-264VAC
Config: Over voltage range (AC)22-29VAC, 108-150VAC, 187-240VAC, 198-242VAC, 216-270VAC
Input frequency (Hz)50-400Hz
Config: Nominal DC Voltage12VDC, 24VDC, 48VDC, 110VDC
Config: Max input voltage (DC)17VDC, 32VDC, 62VDC, 145VDC
Config: Under voltage range (DC)10-13VDC, 19-26VDC, 38-50VDC, 85-121VDC
Config: Over voltage range (DC)11-15VDC, 22-29VDC, 43-58VDC, 99-135VDC
Power consumption+ 2 watts max
Set-point stability± 0.5% of set-point
Polarity protectionDC versions only
Trip response0.5 sec fixed (± 0.1 sec)
Reset time0.1 sec
Output contactsSPDT
Contact rating10A at 240VAC resistive
Expected relay life (Mechanical)10 million operations
Expected relay life (Electrical)100,000 at rated load
Operating temp14° to +122°F
Humidity tolerance97% w/o condensation
Mounting8-pin socket (*order separately)
Case materialABS plastic
Socket Part Number51X120
Warranty5-year Unconditional Warranty

FAQs

What output configuration does the Model 2621 Voltage Monitor provide for system integration?
The Model 2621 features an SPDT (Single Pole Double Throw) output configuration, allowing for versatile control applications. Its relay operation is switch selectable for either 'on low' or 'off low' conditions.
What are the typical voltage ranges and response times for the Model 2621?
The Model 2621 supports nominal AC voltages such as 24VAC, 120VAC, 208VAC, and 240VAC, and DC voltages including 12VDC, 24VDC, 48VDC, and 110VDC. It has a fixed trip response of 0.5 seconds and a reset time of 0.1 seconds.
What are the environmental and durability specifications for the Model 2621?
This voltage monitor operates within a temperature range of 14° to +122°F and tolerates 97% humidity without condensation. Its relay contacts are rated for 10A at 240VAC resistive, with an electrical life of 100,000 operations at rated load.