2621-48VDC
The Model 2621 Voltage Monitor offers precise voltage supervision for critical industrial applications. Its switch-selectable relay operation allows for flexible control logic, accommodating both 'on low' and 'off low' scenarios. With configurable nominal AC voltages including 24VAC, 120VAC, 208VAC, and 240VAC, and DC options like 12VDC, 24VDC, 48VDC, and 110VDC, this device adapts to diverse power systems. A robust 10A at 240VAC resistive contact rating ensures reliable switching for connected loads. The unit maintains set-point stability within ± 0.5% and operates effectively across a 14° to +122°F temperature range, tolerating 97% humidity without condensation. Its rapid 0.5-second trip response and 0.1-second reset time ensure timely system protection. The compact design and 8-pin socket mounting facilitate straightforward integration, providing consistent performance and protection for sensitive equipment.
The Model 2621 dual set point voltage monitor is designed to monitor
single phase equipment. The Normal LED indicates the relay is ENERGIZED.
Toggle switch settings are as follows: Off lo – Relay de-energizes at
Lo Trip – Relay energizes at Hi Trip On lo – Relay energizes at Lo
Trip – Relay de-energizes at Hi Trip The Model 2621 is available in AC
or DC versions. AC models of the 2621 are not frequency sensitive and
can be used on systems from 50 to 400 Hz. Dual set points are ideal for
battery charging applications.
Out of stock
$332.00
Specifications
| Output Configuration | SPDT |
|---|---|
| Relay Operation | Switch Selectable Relay On or Off on Low |
| Switch Position Logic (Off Lo) | Lo Trip Set Point: Relay De-Energizes, Hi Trip Set Point: Relay Energizes |
| Switch Position Logic (On Lo) | Lo Trip Set Point: Relay Energizes, Hi Trip Set Point: Relay De-Energizes |
| Config: Nominal AC voltages | 24VAC, 120VAC, 208VAC, 240VAC |
| Config: Max input voltage (AC) | 32VAC, 160VAC, 220VAC, 285VAC |
| Config: Under voltage range (AC) | 19-26VAC, 90-132VAC, 185-229VAC, 178-233VAC, 200-264VAC |
| Config: Over voltage range (AC) | 22-29VAC, 108-150VAC, 187-240VAC, 198-242VAC, 216-270VAC |
| Input frequency (Hz) | 50-400Hz |
| Config: Nominal DC Voltage | 12VDC, 24VDC, 48VDC, 110VDC |
| Config: Max input voltage (DC) | 17VDC, 32VDC, 62VDC, 145VDC |
| Config: Under voltage range (DC) | 10-13VDC, 19-26VDC, 38-50VDC, 85-121VDC |
| Config: Over voltage range (DC) | 11-15VDC, 22-29VDC, 43-58VDC, 99-135VDC |
| Power consumption | + 2 watts max |
| Set-point stability | ± 0.5% of set-point |
| Polarity protection | DC versions only |
| Trip response | 0.5 sec fixed (± 0.1 sec) |
| Reset time | 0.1 sec |
| Output contacts | SPDT |
| Contact rating | 10A at 240VAC resistive |
| Expected relay life (Mechanical) | 10 million operations |
| Expected relay life (Electrical) | 100,000 at rated load |
| Operating temp | 14° to +122°F |
| Humidity tolerance | 97% w/o condensation |
| Mounting | 8-pin socket (*order separately) |
| Case material | ABS plastic |
| Socket Part Number | 51X120 |
| Warranty | 5-year Unconditional Warranty |