Voltage Sensor

2602-120

The Model 2602 Voltage Sensor provides reliable voltage monitoring for industrial applications. Engineered for consistent performance, this unit operates with a nominal input voltage of 120VAC and features a DPDT output type, rated at 10A at 240VAC resistive. Its automatic reset function ensures continuous operation without manual intervention, enhancing system uptime. With a rapid response time of 28.3ms maximum, it quickly detects voltage fluctuations, safeguarding connected equipment. The sensor is designed to perform in demanding environments, tolerating temperatures from -20° to +140° F and humidity up to 97% without condensation. This robust construction and precise operation contribute to overall system stability and longevity. Furthermore, the unit requires no field adjustments or calibrations, simplifying installation and reducing maintenance overhead. Its expected relay life is 10 million mechanical operations, indicating long-term durability.

Volt Sen Fastdropout

DOWNLOADS:

2602-120

Specifications

Nominal input voltage120VAC
input voltage135VAC
Frequency60Hz
Power consumption2 watts
Drop-out voltage80VAC
Pick-up voltage84VAC
Repeat accuracy (fixed conditions)± 1%
Repeat accuracy (temperature range)± 2% (0°-140° F)
Output TypeDPDT
Output Rating10A at 240VAC resistive
Expected relay life (Mechanical)10 million operations
Expected relay life (Electrical)100,000 oper at rated load
Reset TypeAutomatic
Response time28.3ms
Reset time10 seconds
Operating temperature-20° to +140° F
Humidity tolerance0-97% without condensation
Case materialABS plastic
AdjustmentsNo field adjustments or calibrations
Warrantyone year

FAQs

What are the primary input voltage specifications for the Model 2602 Voltage Sensor?
The Model 2602 operates with a nominal input voltage of 120VAC and can handle a maximum input voltage of 135VAC. Its frequency is 60Hz.
What type of output does the Model 2602 Voltage Sensor provide and what is its rating?
The sensor provides a DPDT output type. Its output rating is 10A at 240VAC resistive.
What are the environmental operating limits and reset characteristics of this voltage sensor?
The Model 2602 functions within an operating temperature range of -20° to +140° F and tolerates 0-97% humidity without condensation. It features an automatic reset type.