Voltage Sensor

2601-110VDC

The MODEL 2601 Voltage Sensor offers essential undervoltage monitoring for critical industrial systems. Its automatic reset function ensures continuous operational integrity, eliminating the need for manual intervention after a fault clears. Precision is maintained through a setpoint stability of ± 0.5% and a rapid 0.5-second fixed trip response, providing timely detection of voltage deviations. The SPDT 10A output contacts at 240VAC resistive allow for versatile integration into control circuits. Engineered for demanding environments, this sensor operates reliably across a temperature range of -20° to +122° F, with a humidity tolerance of 97% without condensation. Its robust ABS plastic enclosure and screwdriver adjustable settings simplify installation and calibration. This unit supports multiple AC and DC nominal voltages, enhancing its adaptability across various power systems. A 5-year unconditional warranty underscores its durability and long-term performance commitment.

Voltage Sensor

DOWNLOADS:

2601-110vdc

Specifications

FunctionMonitors Under Voltage
Output TypeSPDT Output
Reset TypeAutomatic Reset
Warranty5 Year Unconditional Warranty
Config: Nominal AC Voltages24VAC, 120VAC, 208VAC, 240VAC
Config: AC Voltage Range19-24V (for 24VAC), 90-120V (for 120VAC), 185-200V (for 208VAC), 200-240V (for 240VAC)
Config: AC Input Voltage32V (for 24VAC), 160V (for 120VAC), 250V (for 208VAC), 285V (for 240VAC)
Input Frequency (AC)50 - 400 Hz
Config: Nominal DC Voltage12VDC, 24VDC, 28VDC, 48VDC, 110VDC
Config: DC Voltage Range10-12V (for 12VDC), 19-24V (for 24VDC), 22-28V (for 28VDC), 33-48V (for 48VDC), 85-100V (for 110VDC)
Config: DC Input Voltage17V (for 12VDC), 32V (for 24VDC), 37V (for 28VDC), 62V (for 48VDC), 145V (for 110VDC)
Power Consumption2W
Setpoint Stability± 0.5% of setpoint
Dead Band2% or less
Polarity ProtectionDC versions only
Trip Response0.5 second fixed (± 0.1 second)
Reset Time0.1 second
Output ContactsSPDT 10A at 240VAC resistive
Expected Relay Life (Mechanical)10 million operations
Expected Relay Life (Electrical)100,000 at rated load
Operating Temperature-20° to +122° F
Humidity Tolerance97% w/o condensation
Mounting8-pin socket (order separately)
Required Accessory8-pin socket number 51X120
Enclosure MaterialABS plastic
AdjustmentScrewdriver adjustable
Dimension Tolerance± 0.06

FAQs

What are the operating voltage ranges for the MODEL 2601 Voltage Sensor?
The sensor supports nominal AC voltages including 24VAC (19-24V range), 120VAC (90-120V range), 208VAC (185-200V range), and 240VAC (200-240V range). For DC, it supports 12VDC (10-12V range), 24VDC (19-24V range), 28VDC (22-28V range), 48VDC (33-48V range), and 110VDC (85-100V range).
What are the environmental operating limits for this voltage sensor?
The MODEL 2601 operates within a temperature range of -20° to +122° F. It also tolerates up to 97% humidity without condensation, ensuring functionality in varied industrial settings.
How does the MODEL 2601 handle voltage deviations and resets?
It features a fixed trip response of 0.5 seconds (± 0.1 second) for undervoltage detection. The unit incorporates an automatic reset function, with a reset time of 0.1 second once the voltage returns to acceptable levels.